Code
Name
EF4
External Fault (terminal S4) The multi-function digital input terminal
Note:
Perform Fault Reset to clear the fault.
Code
Name
EF5
External Fault (terminal S5) The multi-function digital input terminal
Note:
Perform Fault Reset to clear the fault.
Code
Name
EF6
External Fault (terminal S6) The multi-function digital input terminal
Note:
Perform Fault Reset to clear the fault.
Code
Name
EF7
External Fault (terminal S7) The multi-function digital input terminal
Note:
Perform Fault Reset to clear the fault.
Code
Name
EF8
External Fault (terminal S8) The multi-function digital input terminal
Note:
Perform Fault Reset to clear the fault.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Cause
S4 triggered an external fault via an
external device.
The wiring is incorrect.
External fault [H1-04 = 20 to 2B] is
assigned to MFDI terminal S4 that is not
in use.
Cause
S5 triggered an external fault via an
external device.
The wiring is incorrect.
External fault [H1-05 = 20 to 2B] is
assigned to MFDI terminal S5 that is not
in use.
Cause
S6 triggered an external fault via an
external device.
The wiring is incorrect.
External fault [H1-06 = 20 to 2B] is
assigned to MFDI terminal S6 that is not
in use.
Cause
S7 triggered an external fault via an
external device.
The wiring is incorrect.
External fault [H1-07 = 20 to 2B] is
assigned to MFDI terminal S7 that is not
in use.
Cause
S8 triggered an external fault via an
external device.
The wiring is incorrect.
External fault [H1-08 = 20 to 2B] is
assigned to MFDI terminal S8 that is not
in use.
Possible Solution
1. Identify the device that triggered the external
faults and remove the cause.
2. Clear the external fault input in the multi-
function digital input.
Connect the signal line to multi-function digital
input terminal S4 properly.
Set the multi-function digital input properly.
Possible Solution
1. Identify the device that triggered the external
faults and remove the cause.
2. Clear the external fault input in the multi-
function digital input.
Connect the signal line to multi-function digital
input terminal S5 properly.
Set the multi-function digital input properly.
Possible Solution
1. Identify the device that triggered the external
faults and remove the cause.
2. Clear the external fault input in the multi-
function digital input.
Connect the signal line to multi-function digital
input terminal S6 properly.
Set the multi-function digital input properly.
Possible Solution
1. Identify the device that triggered the external
faults and remove the cause.
2. Clear the external fault input in the multi-
function digital input.
Connect the signal line to multi-function digital
input terminal S7 properly.
Set the multi-function digital input properly.
Possible Solution
1. Identify the device that triggered the external
faults and remove the cause.
2. Clear the external fault input in the multi-
function digital input.
Connect the signal line to multi-function digital
input terminal S8 properly.
Set the multi-function digital input properly.