11.8 H: Terminal Functions
Note:
• This function enables only when the induction motor is used for A1-02 = 8 [Control Method Selection = EZ Open Loop Vector
Control].
• Refer to "b2: DC Circuit Braking" for details.
61: External Speed Search command 1
Setting
Function
61
External Speed
Search command 1
When the terminal is turned ON for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive
starts speed search from the maximum output frequency.
Note:
• If both H1-xx = 61 and 62 are set simultaneously, oPE03 [Multi-Function Input Setting Err] is detected. Set the external speed search
command for only 1 or 2.
• Refer to "b3: Speed Search" for details.
62: External Speed Search command 2
Setting
Function
62
External Speed
Search command 2
When the terminal is turned ON for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive
starts speed search from the frequency reference.
Note:
• If both H1-xx = 61 and 62 are set simultaneously, oPE03 [Multi-Function Input Setting Err] is detected. Set the external speed search
command for only 1 or 2.
• Refer to "b3: Speed Search" for details.
63: Field weakening
Setting
Function
63
Field weakening
Note:
Refer to "d6: Field Weak & Field Force" for details.
65: KEB Ride-Thru 1 (N.C.)
Setting
Function
65
KEB Ride-Thru 1 (N.
C.)
ON : Normal operation
OFF : Deceleration during momentary power loss
When KEB Ride-Thru 1 is enabled, set L2-29 [KEB Method Selection]. The drive operates with the KEB method
that was selected.
Note:
• If KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] are set simultaneously, oPE03 [Multi-Function Input
Setting Err] is detected.
• Refer to "KEB Ride-Thru function" for details.
66: KEB Ride-Thru 1 (N.O.)
Setting
Function
66
KEB Ride-Thru 1 (N.
O.)
ON : Deceleration during momentary power loss
770
V/f
CL-V/f
OLV
CLV
AOLV
Executes speed search using an external reference even when b3-01 = 0 [Speed Search Selection at
Start = Disabled].
V/f
CL-V/f
OLV
CLV
AOLV
Executes speed search using an external reference even when b3-01 = 0 [Speed Search Selection at
Start = Disabled].
V/f
CL-V/f
OLV
CLV
AOLV
This function issues the commands of Field Weakening Level and Field Weakening Frequency
Limit set in d6-01 and d6-02 when the input terminal is turned ON
V/f
CL-V/f
OLV
CLV
AOLV
Switches the KEB1 function between enable and disable via the KEB Ride-Thru 1 (N.C.).
V/f
CL-V/f
OLV
CLV
AOLV
Switches the KEB1 function between enable and disable via the KEB Ride-Thru 1 (N.O.).
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM

Advertisement