YASKAWA GA700 Technical Manual page 790

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
C: Frequency Reference Loss
Setting
Function
C
Frequency Reference
Loss
Note:
Refer to "L4-05: FreqReference Loss Detect Select" for more information.
D: Braking Resistor Fault
Setting
Function
D
Braking Resistor
Fault
E: Fault
Setting
Function
E
Fault
Note:
Parameters CPF00 and CPF01 [Control Circuit Error] are excluded.
F: Through Mode
Setting
Function
F
Through Mode
10: Minor Fault
Setting
Function
10
Minor Fault
11: Fault Reset Command Active
Setting
Function
11
Fault Reset
Command Active
12: Timer Output
Setting
Function
12
Timer Output
Note:
Refer to "b4: Timer Function" for more information.
13: Speed Agree 2
Setting
Function
13
Speed Agree 2
Note:
• The detection function operates regardless of the direction of motor rotation.
• The motor speed is used as the reference when using Closed Loop Vector Control or Closed Loop Vector Control for PM.
790
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when a loss of frequency reference is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the mounting type braking resistor is overheating or the braking
transistor is experiencing a fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive experiences a fault.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting when terminals are not used or to use terminals in through mode. This can be used
as the PLC contact output via MEMOBUS/Modbus or the communication option. This signal does
not function as long as signals from the PLC are not configured.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive experiences a minor fault.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the drive receives the reset command from the control circuit terminal,
serial communications, or the communication option.
V/f
CL-V/f
OLV
CLV
AOLV
This is configured when the timer function is used as an output terminal.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is within the range of the frequency reference ±
L4-04 [Speed Agree Detection Width (+/-)].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV

Advertisement

Table of Contents
loading

Table of Contents