YASKAWA GA700 Technical Manual page 871

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

L8-40: CarrierFreqReduct Off DelayTime
No.
Name
(Hex.)
L8-40
CarrierFreqReduct
Off DelayTime
(04F1)
When L8-40 is set to a value other than 0.00, the carrier frequency reduction function is enabled during startup.
The carrier frequency is automatically reduced when operation starts. After the time set in L8-40 elapses, the
carrier frequency returns to the value set in C6-02 [Carrier Frequency Selection].
When L8-38 = 1, 2 [Carrier Frequency Reduction = Enabled], L8-40 is also applied as the time taken for the
carrier frequency to return to its configured value after being reduced.
L8-41: High Current Alarm Selection
No.
Name
(Hex.)
L8-41
High Current Alarm
Selection
(04F2)
0 : Disabled
An HCA is not detected.
1 : Enabled
An HCA is triggered when the output current exceeds 150% of the drive rated current.
The MFDO terminal set for an alarm [H2-01 to H2-04 = 10] turns on.
L8-51: STPo I Detection Level
No.
Name
(Hex.)
L8-51
STPo I Detection
Level
(0471)
Note:
The detection level is automatically calculated when L8-51 = 0.
L8-52: STPo Integration Level
No.
Name
(Hex.)
L8-52
STPo Integration
Level
(0472)
L8-53: STPo Integration Time
No.
Name
(Hex.)
L8-53
STPo Integration
Time
(0473)
L8-54: STPo Id Diff Detection
No.
Name
(Hex.)
L8-54
STPo Id Diff
Detection
(0474)
0 : Disabled
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time (off delay time) taken for the automatically reduced carrier
frequency to return to the state before the reduction.
V/f
CL-V/f
OLV
CLV
AOLV
Triggers an HCA [Current Alarm] when the output current exceeds 150% of
the drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the STPo [Desynchronization Error] on the basis of the output current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Desynchronization Error] on the basis of
the ACR integral value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time until STPo is detected after the value of L8-51 [STPo I
Detection Level] is exceeded.
V/f
CL-V/f
OLV
CLV
AOLV
Enables or disables the Id deviation detection function for STPo
[Desynchronization Error].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.9 L: Protection Function
Default
(Range)
Determined by A1-02
(0.00 - 2.00 s)
Default
(Range)
0
(0, 1)
Default Setting
(Range)
0.0%
(0.0 - 300.0%)
Default Setting
(Range)
1.0
(0.1 - 2.0)
Default Setting
(Range)
1.0 s
(1.0 - 10.0 s)
Default Setting
(Range)
1
(0, 1)
11
871