YASKAWA GA700 Technical Manual page 174

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

3.11 Test Run Checklist
Checke
No.
d
14
Have E5-01 to E5-24 [PM Motor Parameters] been set?
15
Have C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1] been set?
Checke
No.
d
16
Have E5-01 to E5-24 [PM Motor Parameters] been set?
17
Have C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1] been set?
18
Have F1-01 [PG 1 Pulses Per Revolution] and F1-05 [PG 1 Rotation Selection] been set?
19
Has E5-11 [Encoder Z-Pulse Offset] been set?
After checking Nos. 5 to 19, check the following items.
Checke
No.
d
When operation is started, is "Rdy" displayed on the keypad?
20
When wanting to issue Run commands and frequency references from the keypad, was
21
drive was put in LOCAL mode? (When in LOCAL mode, the LOCAL/REMOTE indicator lights).
During a test run, when the direction of motor rotation was incorrect, were two of the wires of the drive's output
22
terminals (U/T1, V/T2, W/T3) switched?
23
Was C6-01 [Normal / Heavy Duty Selection] set in accordance with the load characteristics?
To ensure that the "electronic thermal protector" functions properly and protects the motor from overheating,
24
were E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload Protection Select] set correctly?
When wanting to receive Run commands and frequency references at the control circuit terminals, was [LO/RE
25
selection key] pressed so the drive was put in REMOTE mode? (When in REMOTE mode, the LOCAL/
REMOTE indicator turns OFF.)
When terminal A1 is to be used for the frequency reference
• Voltage input
– Have you checked to make sure that DIP switch S1-1 inside the drive is at the V position?
– Have H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0-10V (LowLim=0), 0-10V (BipolRef)] been set?
– Has H3-02 = 0 [Terminal A1 Function Selection = Frequency Bias] been set?
26
• Current input
– Have you checked to make sure that DIP switch S1-1 inside the drive is at the I position?
– Has H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4-20 mA, 0-20 mA] been set?
– Has H3-02 = 0 [Terminal A1 Function Selection = Frequency Bias] been set?
When terminal A2 is to be used for the frequency reference
• Voltage input
– Have you checked to make sure that DIP switch S1-2 inside the drive is at the V position?
– Have H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0-10V (LowLim=0), 0-10V (BipolRef)] been set?
– Has H3-10 = 0 [Terminal A2 Function Selection = Frequency Bias] been set?
27
• Current input
– Have you checked to make sure that DIP switch S1-2 inside the drive is at the I position?
– Has H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4-20mA, 0-20mA] been set?
– Has H3-10 = 0 [Terminal A2 Function Selection = Frequency Bias] been set?
174
Table 3.29 PM Advanced Open Loop Vector [A1-02 = 6]
Table 3.30 PM Closed Loop Vector Control [A1-02 = 7]
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual