D4: Frequency Reference Hold And Up/Down 2 Function - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.7 d: Reference Settings

d4: Frequency Reference Hold and Up/Down 2 Function

No.
Name
(Hex.)
d4-01
Freq Reference
Retention Select
(0298)
d4-03
Up/Down 2 Bias
Level
(02AA)
RUN
d4-04
Up/Down 2 Ramp
Selection
(02AB)
RUN
d4-05
Up/Down 2 Bias
Mode Selection
(02AC)
RUN
d4-06
Frequency Ref
Bias (Up/Down 2) Saves the bias value from the Up/Down 2 Command assuming that
(02AD)
d4-07
Analog Freq Ref
Fluctuate Limit
(02AE)
RUN
d4-08
Up/Down 2 Bias
Upper Limit
(02AF)
RUN
d4-09
Up/Down 2 Bias
Lower limit
(02B0)
RUN
d4-10
Up/Down Freq
Lower Limit Select Selects how the lower frequency limit is set when using the Up/
(02B6)
420
Description
V/f
CL-V/f
OLV
CLV
AOLV
Determines whether the frequency reference or the frequency bias
(Up/Down 2) value is saved when the Stop command is entered or
the power supply is shut down.
This parameter is effective when H1-xx [MFDI Function Select] has
been set to one of the following.
• H1-xx = A [Accel/Decel Ramp Hold]
• H1-xx = 10/11 [Up/Down Command]
• H1-xx = 75/76 [Up/Down 2 Command]
The Frequency Reference Hold function depends on which function
it is combined with.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias added to or subtracted from the frequency reference by
the Up/Down 2 function.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the acceleration and deceleration times to use when adding
or subtracting the bias to/from the frequency reference when using
the Up/Down 2 function.
0 : Use selected Accel/Decel time
1 : Use Accel/Decel Time 4
V/f
CL-V/f
OLV
CLV
AOLV
Determines if the bias value is saved to the drive when Up/Down 2
Command [H1-xx = 75, 76] are both released or both enabled. This
parameter is effective only when d4-03 [Up/Down 2 Bias Level] =
0.00.
0 : Hold bias @ no Up/Down selected
1 : 0 bias @ neither/both selected
V/f
CL-V/f
OLV
CLV
AOLV
E1-04 [Maximum Output Frequency] is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
If the frequency reference changes for more than the level set to this
parameter, then the bias value will be held. Parameter E1-04
[Maximum Output Frequency] is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit of the Up/Down 2 bias as a percentage of E1-04
[Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit of the Up/Down 2 bias as a percentage of E1-04
[Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Down function.
0 : d2-02 or Analog (larger level)
1 : d2-02
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
0
677
(0, 1)
0.00 Hz
679
(0.00 - 99.99 Hz)
0
679
(0, 1)
0
680
(0, 1)
0.0%
680
(-99.9 - +100.0%)
1.0%
680
(0.1 - 100.0%)
100.0%
681
(0.0 - 100.0%)
0.0%
681
(-99.9 - 0.0%)
0
681
(0, 1)