oPE05
Run Cmd/Freq Ref Source
Sel Err
Code
Name
oPE06
Control Method Selection
Error
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Cause
The following parameters are set
simultaneously:
• H6-01 ≠ 3 [PG Feedback]
• H1-xx = 7E [FWD/REV Detect (V/f
w/ simplePG)]
The following parameters are set
simultaneously:
• H1-xx = 75/76 [Up/Down 2
Command]
• H3-01, H3-05, H3-09 = 1 [Terminal
A1, A2, A3 Signal Level Select = 0-
10V (BipolRef)]
The settings are contradictory in the
following way:
• A PG-RT3 is attached to the drive.
• H1-xx = 16 [Motor 2 Selection] has
been set.
Cause
The setting to assign the Run command
or frequency reference to an option card
or the pulse train input is incorrect.
Parameter b1-01 = 3 [Frequency
Reference Selection 1 = Option PCB]
has been set, but an option card is not
connected to the drive.
Parameter b1-02 = 3 [Run Command
Selection 1 = Option PCB] has been set,
but an option card is not connected to
the drive.
The following parameters are set
simultaneously:
• b1-01 = 4 [Pulse Train Input]
• H6-01 ≠ 0 [PulseTrain InTerm RP
Func Select ≠ Frequency reference]
The following parameters are set
simultaneously:
• F3-01 = 6 [Digital Input Function
Selection = BCD (5-digit), 0.01 Hz]
• F3-03 = 0, 1 [DI Data Length
Selection = 8bit, 12bit]
The following parameters have been set
while the AI-A3 option card is installed:
• H1-xx = 2 [External Reference 1/2
Selection]
• b1-15 = 3 [Frequency Reference
Selection 2 = Option PCB]
• F2-01 = 0 [Analog Input Function
Selection = 3 channel individual]
Cause
A1-02 = 1, 3, or 7 [Control Method
Selection = CL-V/f, CLV, CLV/PM] has
been set, but a PG option card is not
connected to the drive.
6.6 Parameter Setting Errors
Possible Solution
Correct the parameter settings.
Remove one of the function assignments.
Correct the parameter settings.
Note:
Motor Switch function is not available when
using the PG-RT3..
Possible Solution
Correct the parameter settings.
Connect an option card to the drive.
Set H6-01 = 0.
Set F3-03 = 2 [16bit].
Correct the parameter settings.
Possible Solution
• Connect a PG option card to the drive.
• Set A1-02 correctly.
6