YASKAWA GA700 Technical Manual page 787

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

2: Speed Agree 1
Setting
Function
2
Speed Agree 1
Note:
• The detection function operates regardless of the direction of motor rotation.
• When using Closed Loop Vector Control, the motor speed is used as the reference.
ON : The output frequency is within the range of "frequency reference ± L4-02."
OFF : The output frequency does not match the frequency reference even though the drive is
running.
3: User-set Speed Agree 1
Setting
Function
3
User-set Speed Agree
1
Note:
• The detection function operates regardless of the direction of motor rotation. The value of L4-01 is used as the forward/reverse
detection level.
• When using Closed Loop Vector Control, the motor speed is used as the reference.
ON : The output frequency is within the range as defined by the result of "L4-01 ± L4-02" and the
range of frequency reference ± L4-02.
OFF : The output frequency is not within the range of "L4-01 ± L4-02" or the range of frequency
reference ± L4-02.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is within the range of the frequency reference ±
L4-02 [Speed Agree Detection Width].
Figure 11.87 Speed Agree 1 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is within the range of L4-01 [Speed Agree
Detection Level] ± L4-02 [Speed Agree Detection Width] and within the range of the frequency
reference ± L4-02.
Figure 11.88 User-defined Speed Agree 1 Time Chart
11.8 H: Terminal Functions
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11
787