YASKAWA GA700 Technical Manual page 742

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.7 F: Options
F6-50: DeviceNet MAC Address
No.
Name
(Hex.)
F6-50
DN MAC Address
(03C1)
Note:
Set a MAC address that is unique. Do not set this parameter to a value of 0. If the parameter is set incorrectly, the ERR on the option
card flashes, and the drive will detect the AEr [Station Address Setting Error].
F6-51: DeviceNet Baud Rate
No.
Name
(Hex.)
F6-51
DN Baud Rate
(03C2)
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from network
The communications speed is set by the controller.
4 : Detect automatically
The drive detects the network communication speed and automatically adjusts the communications speed
accordingly.
F6-52: DeviceNet PCA Setting
No.
Name
(Hex.)
F6-52
DeviceNet PCA
Setting
(03C3)
Note:
The setting value will be reset to default settings if the combination of F6-52 [DeviceNet PCA Setting] and F6-53 [DeviceNet PPA
Setting] is not correct.
F6-53: DeviceNet PPA Setting
No.
Name
(Hex.)
F6-53
DeviceNet PPA
Setting
(03C4)
Note:
The setting value will be reset to default settings if the combination of F6-52 [DeviceNet PCA Setting] and F6-53 [DeviceNet PPA
Setting] is not correct.
F6-54: DeviceNet Idle Fault Detection
No.
Name
(Hex.)
F6-54
DN Idle Flt Det
(03C5)
0 : Enabled
1 : Disabled, no fault detection
An EF0 is not detected.
742
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MAC address for DeviceNet communication. The drive must be
restarted when the setting is changed.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the communications speed for DeviceNet communication. The drive
must be restarted when the setting is changed.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the format of data sent from the DeviceNet communication master to
the drive.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the format of data sent from the drive to the DeviceNet communication
master.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether or not to detect issues of EF0 [Option Card External Fault]
when data is not received from the DeviceNet master.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
0
(0 - 64)
Default Setting
(Range)
0
(0 - 4)
Default Setting
(Range)
21
(0 - 255)
Default Setting
(Range)
71
(0 - 255)
Default Setting
(Range)
0
(0 - 4)