YASKAWA GA700 Technical Manual page 220

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

4.3 UL Standards
1 : Variable Torque
Use this setting for general-purpose motors with a base frequency of 60 Hz.
The motor has less cooling capability in the low speed range because the cooling fan slows down and there is
lower overload tolerance as the speed drops. The trigger point for the electronic thermal protector changes
according to the overload tolerance characteristics of the motor. This provides motor overheat protection from low
speed to high speed across the entire speed range.
Load tolerance
2 : Constant Torque 10:1 Speed Range
Use this setting for drive dedicated motors with a speed range for constant torque of 1:10.
The speed control for this motor is 10% to 100% when at 100% load. Operating slower than 10% speed at 100%
load will trigger motor overload.
Load tolerance
3 : Constant Torque 100:1 SpeedRange
Use this setting for vector motors with a speed range for constant torque of 1:100.
The speed control for this motor is 1 % to 100% when at 100% load. Operating slower than 1% speed at 100%
load will trigger motor overload.
Load tolerance
220
Cooling Ability
Motor designed to operate from line power.
The motor has maximum cooling capability
when operating at a 60 Hz base frequency.
Cooling Ability
This motor is designed to withstand
increasing temperature during continuous
operation even in the low speed range (10%
base frequency).
Cooling Ability
This motor is designed to withstand
increasing temperature during continuous
operation even in the low speed range (1%
base frequency).
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Overload Characteristics (at 100%
motor load)
The drive detects oL1 when operating at
frequencies lower than 60 Hz. The drive
triggers a fault relay output and the motor
coasts to stop.
Overload Characteristics (at 100%
motor load)
The motor operates continuously at 10% to
100% base frequency.
Overload Characteristics (at 100%
motor load)
The motor operates continuously at 1% to
100% base frequency. Motor overload is
triggered when operating slower than 1%
speed at 100% load.