YASKAWA GA700 Technical Manual page 629

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

b5-36: PID Feedback High Detection Lvl
No.
Name
(Hex.)
b5-36
PID Feedback High
Detection Lvl
(01A1)
The drive detects that Excessive PID Feedback [FbH] when the feedback signal rises above the level set in b5-36
for the time set in b5-37 [PID Feedback High Detection Time].
b5-37: PID Feedback High Detection Time
No.
Name
(Hex.)
b5-37
PID Feedback High
Detection Time
(01A2)
b5-38: PID Setpoint User Display
No.
Name
(Hex.)
b5-38
PID Setpoint User
Display
(01FE)
The drive uses this parameter in combination with b5-39 [PID Setpoint Display Digits].
The drive applies user-set PID setpoint and display units to U5-01 [PID Feedback] and U5-04 [PID Setpoint]
when parameter b5-20 = 3 [PID Setpoint Scaling = User Units].
b5-39: PID Setpoint Display Digits
No.
Name
(Hex.)
b5-39
PID Setpoint Display
Digits
(01FF)
The drive uses this parameter in combination with b5-38 [PID Setpoint User Display].
The drive applies user-set PID setpoint and display units to U5-01 [PID Feedback] and U5-04 [PID Setpoint]
when parameter b5-20 = 3 [PID Setpoint Scaling = User Units].
0 : No decimal places 1
1 : One decimal place
2 : Two decimal places
3 : Three decimal places
b5-40: Frequency Reference Monitor @PID
No.
Name
(Hex.)
b5-40
Frequency Reference
Monitor @PID
(017F)
0 : with PID
Monitor U1-01 displays the frequency reference increased or reduced for the PID output.
1 : without PID
Monitor U1-01 displays the frequency value.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the level that triggers Excessive PID Feedback [FbH] as a percentage
of E1-04 [Maximum Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time that triggers Excessive PID Feedback [FbH] when the
feedback signal rises above the level set in b5-36 [PID Feedback High
Detection Lvl].
V/f
CL-V/f
OLV
CLV
AOLV
Determines the value for setting and displaying U5-01, U5-04 when
outputting the maximum output frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of digits for setting and displaying the PID setpoint.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the contents displayed in monitor U1-01 [Freq Reference] when
using PID control.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.3 b: Application
Default
(Range)
100%
(0 - 100%)
Default
(Range)
1.0 s
(0.0 - 25.5 s)
Default
(Range)
Determined by b5-20
(1 - 60000)
Default
(Range)
Determined by b5-20
(0 - 3)
Default
(Range)
0
(0, 1)
11
629

Advertisement

Table of Contents
loading

Table of Contents