Enable Simple Closed Loop V/f Mode
1. Connect the encoder output pulse wiring to terminal RP.
2. Set A1-02 = 0 [Control Method Selection = V/f Control].
3. Set H6-01 = 3.
4. Set H6-02 [Pulse Train Input Scaling] to the speed feedback (pulse train input signal) frequency at the time
when the frequency reference is 100%.
Confirm that H6-04 [Pulse Train Input Bias] is 0% and H6-03 [Pulse Train Input Gain] is 100%.
5. Select the detection method for the direction of motor rotation.
Set H1-xx to 7E when using an MFDI.
6. Set C5 parameters related to ASR gain and integral time to adjust responsiveness.
Note:
• C5 parameters appear when A1-02 = 0 and H6-01 = 3.
• The simple Closed Loop V/f Control mode cannot be used in conjunction with the Motor Switch function.
H6-02: Pulse Train Input Scaling
No.
Name
(Hex.)
H6-02
Pulse Train Input
Scaling
(042D)
RUN
H6-03: Pulse Train Input Gain
No.
Name
(Hex.)
H6-03
Pulse Train Input
Gain
(042E)
RUN
H6-04: Pulse Train Input Bias
No.
Name
(Hex.)
H6-04
Pulse Train Input
Bias
(042F)
RUN
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Figure 11.112 Simple Closed Loop Speed Control Block Diagram
V/f
CL-V/f
OLV
CLV
Sets the frequency of the pulse train input signal used when the item
selected with H6-01 [PulseTrain InTerm RP Func Select] is input at 100%.
V/f
CL-V/f
OLV
CLV
Sets the gain used when the item configured with H6-01 [PulseTrain
InTerm RP Func Select] is input to terminal RP.
V/f
CL-V/f
OLV
CLV
Sets the bias used when the item configured with H6-01 [PulseTrain InTerm
RP Func Select] is input to terminal RP. Sets a value at the time when the
pulse train is 0 Hz.
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default
(Range)
1440 Hz
(100 - 32000 Hz)
Default
(Range)
100.0%
(0.0 - 1000.0%)
Default
(Range)
0.0%
(-100.0 - 100.0%)
11
821