3.10
Fine Tuning during Test Runs (Adjustment of Control
Functionality)
The following explains the adjustment procedures to follow when issues such as hunting or oscillation attributable
to control functionality occur during a test run. Adjust the relevant parameters appearing in the chart, in
accordance with the control method being used and the drive's status.
Note:
In this section, only the parameters that are frequently adjusted are listed. Please consult with a Yaskawa representative if adjustments
having a higher degree of precision are required.

V/f Control and Closed Loop V/f Control

Table 3.16 Parameters for Fine Tuning the Drive (V/f Control and Closed Loop V/f Control Methods)
Issue
Hunting, oscillation at
n1-02 [Hunting
middle-range speeds (10
Prevention Gain Setting]
Hz to 40 Hz)
• The motor excitation
sound is significant.
• Hunting, oscillation at
C6-02 [Carrier Frequency
low speeds (10 Hz or
Selection]
lower), or at middle-
range speeds (10 Hz to
40 Hz)
• Torque, speed response
C4-02 [Torque
is slow.
Compensation Delay
Time]
• Hunting, oscillation
• Insufficient torque at
low speeds (10 Hz or
C4-01 [Torque
lower).
Compensation Gain]
• Hunting, oscillation
• Insufficient torque at
• E1-08 [Mid Point A
low speeds (10 Hz or
lower).
• E1-10 [Minimum
• Significant shock upon
startup.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual

3.10 Fine Tuning during Test Runs (Adjustment of Control Functionality)

Parameter Number
• Reduce setting value
when torque is
insufficient with heavy
loads.
• If hunting, oscillation
occurs with light loads,
increase the setting
value.
• If hunting occurs with a
low-inductance motor,
such as a motor with a
larger frame size or a
high-frequency motor,
lower the setting value.
• Raise the carrier
frequency if the motor
excitation sound is
significant.
• Lower the carrier
frequency if hunting or
oscillation occurs at
low or middle-range
speeds.
• Reduce setting value
when torque, speed
response is slow.
• If hunting, oscillation
occurs, increase the
setting value.
• Increase setting value
when torque is
insufficient at low
speeds.
• If hunting, oscillation
occurs with light loads,
reduce the setting
value.
• Increase setting value
when torque is
insufficient at low
Voltage]
speeds.
• Reduce setting value if
Output Voltage]
there is marked shock
upon drive startup.
Solution
Default Setting
1.00
1(2 kHz)
*1
200 ms
*2
1.00
• E1-08: 15.0 V
• E1-10: 9.0 V
Suggested Setting
0.10 - 2.00
1 to upper limit value
100 - 1000 ms
0.50 - 1.50
*3
Default setting +/- 5 V
*3
3
*4
163