The Initial Rotor Position Estimated Current is the current used to detect the initial position of rotors.
If the motor nameplate has an "Si" item, set the value found there.
■
n8-02: Pole Attraction Current
No.
Name
(Hex.)
n8-02
Pole Attraction
Current
(0541)
The polar pull-in current is the current used to attract the rotor upon completion of detection of the initial rotor
position. When the value set in n8-02 is increased, the starting torque also increases.
• If the motor does not track properly at the time of the polar attraction, increase the value in increments of 10%.
If the value is set too high, oL2 [Drive Overloaded] may be detected.
• If the motor oscillates at the time of the polar attraction, reduce the value in increments of 10%.
Note:
This is effective when set to A1-02 = 7 [Control Method Selection = PM Closed Loop Vector Control] and carrying out Rotational
Auto-Tuning or Z Pulse Offset Tuning.
■
n8-03: Current Starting Time
No.
Name
(Hex.)
n8-03
Current Starting Time
(0542)
Sets the time that the pull-in current is to start when detecting the motor magnetic pole of the rotors.
Note:
If the motor oscillates at the time of the polar attraction, increase the value in increments of 0.5 s. If the value is set too high, oL2 [Drive
Overloaded] may be detected.
■
n8-04: Polar Attraction Time
No.
Name
(Hex.)
n8-04
Polar Attraction Time
(0543)
Sets the amount of time that the pull-in current is to flow when detecting the motor magnetic pole of the rotors.
Note:
If the motor oscillates at the time of the polar attraction, increase the value in increments of 0.5 s. If the value is set too high, oL2 [Drive
Overloaded] may be detected.
■
n8-11: Induction Volt Estimation Gain 2
No.
Name
(Hex.)
n8-11
Induction Volt
Estimation Gain 2
(054A)
Note:
At the default settings, with a setting of n8-72 = 0 [Speed Estimation Method Select = Conventional method], this will be 50.0. With a
setting of n8-72 = 1 [Speed Estimation Method Select = A1000 method], this will be 30.0.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current at the time of polar attraction as a percentage of the motor
rated current, which is deemed to be 100%. Normally there is no need to
change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount for the Current Starting Time, which is used when carrying
out Z Pulse Offset Tuning. Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the amount for the Polar Attraction Time, which is used when carrying
out Z Pulse Offset Tuning. Normally there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for speed estimation. Normally there is no need to change this
setting.
11.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Range)
80%
(0 - 150%)
Default Setting
(Range)
1.5 s
(1.5 - 5.0 s)
Default Setting
(Range)
1.5 s
(1.5 - 5.0 s)
Default Setting
(Range)
Determined by n8-72
(0.0 - 1000.0)
11
889