L1-04: Motor OH Fault Operation Select
No.
Name
(Hex.)
L1-04
Motor OH Fault
Operation Select
(0483)
0 : Ramp to stop
The drive ramps the motor to stop according to the deceleration time. Fault relay output terminal MA-MC will
turn on, and MB-MC will turn off.
1 : Coast to stop
The drive shuts off output and the motor coasts to stop. Fault relay output terminal MA-MC will turn on, and MB-
MC will turn off.
2 : Fast Stop
The drive stops the motor using the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal
MA-MC will turn on, and MB-MC will turn off.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Selects the drive operation when the PTC input signal input into the drive
reaches the detection level of oH4 [Motor Overheat Failure].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
4.3 UL Standards
Default Setting
(Range)
1
(0 - 2)
4
223