9.6 Drive Derating

Altitude Derating

Drive installations presumed to be located at altitudes of 1000 m (3281 ft.) or less.
Derate the output current by 1% for every 100 m (328 ft.) to install the drive in altitudes between 1000 m to 3000
m (3281 ft. to 9843 ft.).
Rated voltage derating is not required:
• when installing the drive at 2000 m (6562 ft.) or lower
• if the drive is grounded with the neutral network when installing the drive at an altitude between 2000 m to
3000 m (6562 ft. to 9843 ft.)
Contact Yaskawa or your nearest sales representative when the drive is not grounded with the neutral network.