H4-03: FM Analog Output Bias
No.
Name
(Hex.)
H4-03
Terminal FM Analog
Output Bias
(041F)
RUN
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). The signal level can be
selected with H4-07 [MFAO Term FM Signal Level Select].
H4-04: MFAO Terminal AM Monitor Select
No.
Name
(Hex.)
H4-04
Terminal AM Analog
Output Select
(0420)
Note:
• The configurable monitor data varies depending on the control mode.
• Set this parameter to 000 or 031 to use in through mode. The terminal AM output level can be set from the PLC via MEMOBUS/
Modbus or the communication option.
H4-05: AM Analog Output Gain
No.
Name
(Hex.)
H4-05
Terminal AM Analog
Output Gain
(0421)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). The signal level can be
selected with H4-08 [MFAO Term AM Signal Level Select].
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in the following example, the voltage
of AM terminal outputs at 5 V (50% of 10 V). Consequently, the output current at the time the AM terminal
outputs a maximum voltage of 10 V will be 200% of the drive rated current.
• H4-04 = 103 [MFAO Terminal AM Monitor Select = Output Current]
• H4-05 = 50.0%
• H4-06 = 0.0% [AM Analog Output Bias = 0.0%]
• H4-08 = 0 [0 to 10 V]
H4-06: AM Analog Output Bias
No.
Name
(Hex.)
H4-06
Terminal AM Analog
Output Bias
(0422)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). The signal level can be
selected with H4-08 [MFAO Term AM Signal Level Select].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitoring signal that is output from the MFAO
terminal FM as a percentage. Set the level of the analog signal output from
the FM terminal at 10 V (or 20 mA) as 100% when an output for monitoring
items is 0%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitoring number to be output from the MFAO terminal AM.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the monitor signal that is output from the MFAO terminal
AM as a percentage. Sets the level of the analog signal output from the AM
terminal when an output of 0% for monitoring items is 0 V (or 4 mA) and
when an output for monitoring items is 100%, and sets 10 V (or 20 mA) as
100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the monitoring signal that is output from the MFAO
terminal AM as a percentage. Set the level of the analog signal output from
the AM terminal at 10 V (or 20 mA) as 100% when an output for
monitoring items is 0%
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default Setting
(Range)
0.0%
(-999.9 - 999.9%)
Default
(Range)
103
(000 - 999)
Default Setting
(Range)
50.0%
(-999.9 - 999.9%)
Default Setting
(Range)
0.0%
(-999.9 - 999.9%)
11
815