11.8 H: Terminal Functions
H5-05: Comm Fault Detection Select
No.
Name
(Hex.)
H5-05
Comm Fault
Detection Select
(0429)
A CE error is detected if the drive does not receive any data from the master during the time configured with H5-
09 [CE Detection Time].
0 : Disabled
Does not perform CE detection. The drive continues operation.
1 : Enabled
Performs CE detection. If a CE error is detected, operation is performed in accordance with the setting of H5-04
[Stopping Method after Com Error].
H5-06: Drive Transmit Wait Time
No.
Name
(Hex.)
H5-06
Drive Transmit Wait
Time
(042A)
H5-09: CE Detection Time
No.
Name
(Hex.)
H5-09
CE Detection Time
(0435)
H5-10: Unit Sel forMEMOBUS/Modbus 0025H
No.
Name
(Hex.)
H5-10
Unit Sel
forMEMOBUS/
(0436)
Modbus 0025H
0 : 0.1 V units
1 : 1 V units
H5-11: Communications ENTER Func Select
No.
Name
(Hex.)
H5-11
Communications
ENTER Func Select
(043C)
0 : Enter Required
818
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to detect CE [MEMOBUS/Modbus Communication Err]
issues during MEMOBUS/Modbus communications.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time to wait to send a response message after the drive receives a
command message from the master.
Figure 11.110 Drive Transmit Wait Time
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for CE [MEMOBUS/Modbus Communication Err]
issues when communication is disrupted.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the unit of measure used for the MEMOBUS/Modbus
communications monitor register 0025H (output voltage reference monitor).
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether or not the Enter command is required to change parameters
via MEMOBUS/Modbus communications.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
1
(0, 1)
Default
(Range)
5 ms
(0 - 65 ms)
Default
(Range)
2.0 s
(0.0 - 10.0 s)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)

Advertisement

Table of Contents
loading