n6-01: Online Tuning Selection
No.
Name
(Hex.)
n6-01
Online Tuning
Selection
(0570)
0 : Disabled
1 : Line-to-line resistance tuning
The drive adjusts the motor line-to-line resistance during run. This procedure is effective for speed values up to 6
Hz and improves the overload capacity in the low speed range by adjusting the value set for the motor resistance.
2 : VoltageAdjustm
The drive adjusts the output voltage during run to improve overload tolerance and minimize the effects of high
temperatures on speed accuracy.
Note:
Setting 2 is enabled only when b8-01 = 0 [Energy Saving Control Selection = Disabled].
n6-05: Online Tuning Gain
No.
Name
(Hex.)
n6-05
Online Tuning Gain
(05C7)
When using motors with a large secondary circuit time constant, reduce the setting value.
If oL1 [Motor Overload] is detected, increase the setting value in 0.1 increments.
n6-11: online resister tuning
No.
Name
(Hex.)
n6-11
online resister tuning
(1B56)

n7: EZ Drive

The n7 parameters provide special adjustments for EZ Open Loop Vector Control.
n7-01: Flux Estimation Cut-off Freq
No.
Name
(Hex.)
n7-01
Flux Estimation Cut-
off Freq
(3111)
Note:
• If oscillation occurs in the low speed range, either lengthen the acceleration time, or raise the setting value in 0.5 increments.
• To obtain starting torque by means of the setting for C4-01 [Torque Compensation Gain], reduce the setting value in 0.3 increments.
n7-05: Torque Control Response Gain
No.
Name
(Hex.)
n7-05
Torque Control
Response Gain
(3115)
Note:
To improve tracking with respect to load changes, increase the setting value in increments of 5. If oscillation occurs during load changes
reduce the setting value in increments of 5.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Selects the type of motor data Online Tuning uses for OLV control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the compensation gain when set to n6-01 = 2 [Online Tuning Selection
= VoltageAdjustm]. Normally there is no need to configure this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Adjusts the responsiveness for online resister tuning. To be enabled, the
value should be set to approximately 1.000. This is disabled if the value is
set to 0.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the oscillation suppression gain for the low speed range.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the response gain relative to load changes.
11.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0 - 2)
Default Setting
(Range)
1.0
(0.1 - 50.0)
Default Setting
(Range)
0.000
(0.000 - 1.000)
Default
(Range)
1.0
(0.1 - 10.0)
Default Setting
(Range)
100
(10 - 1000)
11
887