H2 MFDO Parameters

H2-01: Terminal M1-M2 Function Select
No.
Name
(Hex.)
H2-01
Term M1-M2
Function Selection
(040B)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-02: Terminal M3-M4 Function Select
No.
Name
(Hex.)
H2-02
Term M3-M4
Function Selection
(040C)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-03: Terminal P1-PC Function Select
No.
Name
(Hex.)
H2-03
Terminal P1-PC
Function Select
(040D)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-04: Terminal P2-PC Function Select
No.
Name
(Hex.)
H2-04
Terminal P2-PC
Function Select
(040E)
Note:
Set this parameter to F when not using the terminal or to use the terminal in through mode.
H2-06: Watt Hour Output Unit Selection
No.
Name
(Hex.)
H2-06
Watt Hour Output
Unit Selection
(0437)
This output is input to the Watt hour meter or PLC via a 200 ms pulse signal. Each pulse is output by the kWh unit
selected by H2-06.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Selects the function assigned to MFDO terminal M1-M2.
V/f
CL-V/f
OLV
CLV
Selects the function assigned to MFDO terminal M3-M4.
V/f
CL-V/f
OLV
CLV
Selects the function assigned to MFDO terminal P1-C1.
V/f
CL-V/f
OLV
CLV
Selects the function assigned to MFDO terminal P2-C2.
V/f
CL-V/f
OLV
CLV
Configures the output signal unit when H2-01 through H2-04 = 39 [MFDO
Function Select = Watt Hour Pulse Output] is selected.
Figure 11.84 Example MFDO when Configured for Watt Hours
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default
(Range)
0
(0 - 1A7)
Default Setting
(Range)
1
(0 - 1A7)
Default Setting
(Range)
2
(0 - 1A7)
Default Setting
(Range)
F
(0 - 1A7)
Default Setting
(Range)
0
(0 - 4)
11
779