YASKAWA GA700 Technical Manual page 721

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
• Refer to H1-xx "Multi-function Digital Input Setting Values" for more information on multi-function digital input setting values.
• Values 0 [3-Wire Sequence] and 20 through 2F [External fault] cannot be selected for F3-10 through F3-25.
• Configure such that F3-10 through F3-25 = F [Through Mode] when not using the DI-A3 multi-function input. Note that Through
mode is not supported.
• Terminal Dx of the DI-A3 is read twice in accordance with the setting of b1-06 [Digital Input Reading].
• Configuring such that F3-01 = 8 when DI-A3 is the frequency reference source (b1-01 or b1-15 = 3 [Frequency Reference Selection 1/
2 = Option PCB]) results in the detection of oPE05 [Run Cmd/Freq Ref Source Sel Err].
• The following functions can be used together with the DI-A3 multi-function input.
–H1-40 through H1-42 [Extend MFDI 1 Function Selection through Extend MFDI 3 Function Selection]
–H7-01 through H7-04 [Virtual MF Digital Inputs 1 through 4]
F3-01: Digital Input Function Selection
No.
Name
(Hex.)
F3-01
Digital Input
Function Selection
(0390)
Note:
The DI-A3 input method is set to the BCD input method regardless of the setting of F3-01 when o1-03 = 2 or 3 [r/min or User-selected
units]. In this scenario, the value set in o1-03 is used as the setting unit.
0 : BCD, 1% units
1 : BCD, 0.1% units
2 : BCD, 0.01% units
3 : BCD, 1 Hz units
4 : BCD, 0.1 Hz units
5 : BCD, 0.01 Hz units
6 : BCD (5-digit), 0.01 Hz
7 : Binary input
The setting unit and setting range vary depending on the value set in F3-03 [DI Data Length Selection].
• F3-03 = 0 [8 bit]: 100%/255 (-255 to +255)
• F3-03 = 1 [12 bit]: 100%/4095 (-4095 to +4095)
• F3-03 = 2 [16 bit]: 100%/30000 (-33000 to +33000)
8 : Multi-function Digital input
The DI-A3 card is also used as a multi-function digital input terminal.
F3-03: DI Data Length Selection
No.
Name
(Hex.)
F3-03
DI Data Length
Selection
(03B9)
0 : 8bit
1 : 12bit
2 : 16bit
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Selects the data format of digital input signals. This parameter is enabled
when o1-03 = 0 or 1 [Keypad Display Selection = 0.01 Hz or 0.01% (100%
= E1-04)].
V/f
CL-V/f
OLV
CLV
AOLV
Selects the number of bits used to set the frequency reference with DI-A3.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.7 F: Options
Default
(Range)
0
(0 - 8)
Default Setting
(Range)
2
(0 to 2)
11