11.6 E: Motor Parameters
Note:
Be aware of the following points when manually setting V/f patterns.
• To set linear V/f characteristics at frequencies lower than that of E1-06, set E-07 = E1-09. In this case, the setting for E1-08 will be
disregarded.
• Ensure that the five frequencies are set according to the following rules to prevent triggering oPE10 [V/f Data Setting Error];
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
• Parameter E1-03 is not reset when the drive is initialized using A1-03.
E1-01: Input AC Supply Voltage
No.
Name
(Hex.)
E1-01
Input AC Supply
Voltage
(0300)
NOTICE: Set parameter E1-01 [Input AC Supply Voltage] to match the input voltage of the drive. Drive input voltage (not motor
voltage) must be set in E1-01 for the protective features to function properly. Failure to set the correct drive input voltage will
result in improper drive operation.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value used for the motor protective functions listed in the following table. The
detection level changes for some motor protective functions when using a 400 V class drive.
Voltage
E1-01 Setting
200 V class
All settings
Setting value ≥
400 V
400 V class
Setting value <
400 V
*1
This is the protection function enabled in drives with a built-in braking transistor. Figures indicate the level that triggers the built-in
braking transistor. Refer to "YASKAWA AC Drive 72060001 Series Option Braking Unit and Braking Resistor Unit Installation
Manual (TOBPC72060001)."
E1-03: V/f Pattern Selection
No.
Name
(Hex.)
E1-03
V/f Pattern Selection
(0302)
690
Figure 11.68 V/f Pattern
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive input voltage. Set this parameter to the nominal voltage of the
AC power supply.
BTR Operation
Level
ov Detection
Level
(rr Detection
Level)
410 V
394 V
820 V
788 V
820 V
788 V
V/f
CL-V/f
OLV
CLV
AOLV
Selects the V/f pattern for the drive and motor from 15 predefined patterns
(settings: 0 through E) or creates a custom V/f pattern(setting: F).
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Approximate Values
L2-05
[Undervoltage
Detect Level
(Uv1)]
*1
190 V
380 V
350 V
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
200 V Class: 200 V,
400 V: 400 V
(200 V Class: 155 to
255 V, 400 V Class:
310 to 510 V)
L2-11
L3-17
[DC Bus Vol
[DC Bus Reg
Setpoint during
Level]
KEB]
260 V
375 V
500 V
750 V
460 V
750 V
Default
(Range)
F
(Determined by A1-
02)