YASKAWA GA700 Technical Manual page 709

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

E9-05: Base Voltage
No.
Name
(Hex.)
E9-05
Base Voltage
(11E8)
The value of E9-05 is automatically set to the value input for [Base Voltage] by the EZ Tuning process.
E9-06: Motor Rated Current
No.
Name
(Hex.)
E9-06
Motor Rated Current
(11E9)
Note:
Values appear in the following units.
• 2004 to 2042, 4002 to 4023: 0.01 A units
• 2056 to 2415, 4031 to 4675: 0.1 A units
The setting value of E9-06 is the reference value for motor protection. Enter the motor rated current as written on
the motor nameplate. The value of E9-06 is automatically set to the value input for [Motor Rated Current] by the
Auto-Tuning process for motor parameter settings.
E9-07: Motor Rated Power (kW)
No.
Name
(Hex.)
E9-07
Motor Rated Power
(kW)
(11EA)
The value of E9-07 is automatically set to the value input for [Motor Rated Power (kW)] by the Auto-Tuning
process for motor parameter settings.
Note:
The value appears in units of 300 kW when the maximum applicable motor output is less than 0.01 kW and appears in units of 300 kW
when over 0.1 kW.
E9-08: Motor Pole Count
No.
Name
(Hex.)
E9-08
Motor Pole Count
(11EB)
The value of E9-08 is automatically set to the value input for [Number of Motor Poles] by the Auto-Tuning
process for motor parameter settings.
E9-09: Motor Rated Slip
No.
Name
(Hex.)
E9-09
Motor Rated Slip
(11EC)
The setting value of E9-09 is the slip compensation reference value.
Parameter E9-09 is automatically calculated with the setting values of E9-03, E9-04, and E9-08. The value of E9-
09 is automatically set to the value input for [Motor Rated Slip] by the Auto-Tuning process for motor parameter
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Configures the rated voltage of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated current in amperes.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated power in 0.01 kW. (1 HP = 0.746 kW)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the motor rated slip.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.6 E: Motor Parameters
Default Setting
(Range)
Determined by E9-01
(200 V Class: 0.0 to
255.0 V,
400 V Class: 0.0 to
510.0 V)
Default Setting
(Range)
Determined by E9-01
and o2-04
(10% to 200% of the
drive rated current)
Default Setting
(Range)
Determined by E9-02
and o2-04
(0.00 - 650.00 kW)
Default Setting
(Range)
4
(2 to 48)
Default Setting
(Range)
0.0 Hz
(0.0 - 20.0 Hz)
709