YASKAWA GA700 Technical Manual page 805

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

The current signal is 0 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal
due to gain and bias settings will be read as 0%.
Note:
When H3-09 = 0, 1, set DIP switch S1-2 to the V side (voltage). When H3-09 = 2, 3, set DIP switch S1-2 to the I side (current). The
default setting is the I side (current).
H3-10: Terminal A2 Function Selection
No.
Name
(Hex.)
H3-10
Terminal A2
Function Selection
(0418)
H3-11: Terminal A2 Gain Setting
No.
Name
(Hex.)
H3-11
Terminal A2 Gain
Setting
(0419)
RUN
Parameter H3-03 sets the reference amount for the function set for terminal A2 as a percentage when 10 V (or 20
mA) is input.
AUse H3-11 and H3-12 [Terminal A2 Bias Setting] to adjust the characteristics of the analog input signal to
terminal A2.
H3-12: Terminal A2 Bias Setting
No.
Name
(Hex.)
H3-12
Terminal A2 Bias
Setting
(041A)
RUN
This parameter sets the bias for the function set for terminal A2 as a percentage when 0 V (4 mA or 0 mA) is
input.
Use H3-11 [Terminal A2 Gain Setting] and H3-12 to adjust the characteristics of the analog input signal to
terminal A2.
H3-13: Analog Input FilterTime Constant
No.
Name
(Hex.)
H3-13
Analog Input
FilterTime Constant
(041B)
Applying the primary delay filter to the analog input enables an analog input signal without high-frequency noise
components to be obtained. An analog input filter prevents erratic drive control. Drive operation becomes more
stable as the programmed time becomes longer, but it also becomes less responsive to rapidly changing analog
signals.
H3-14: Analog Input Term Enable Select
No.
Name
(Hex.)
H3-14
Analog Input
Terminal Enable Sel
(041C)
The terminals not set as the target are not influenced by input signals.
1 : Terminal A1 only
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Selects a function set to the MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of the analog signal to be input to the MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias of the analog signal to be input to the MFAI terminal A2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant when applying a primary delay filter to the MFAI
terminal.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the enabled terminal Sx when H1-xx = C [Terminal Sx Function
Selection = Analog Terminal Enable Selection] is ON. Also selects the
disabled terminal Sx when the input is OFF.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.8 H: Terminal Functions
Default Setting
(Range)
0
(0 - 32)
Default Setting
(Range)
100.0%
(-999.9 - +999.9%)
Default Setting
(Range)
0.0%
(-999.9 - +999.9%)
Default Setting
(Range)
0.03 s
(0.00 - 2.00 s)
Default Setting
(Range)
7
(1 - 7)
11
805