YASKAWA GA700 Technical Manual page 798

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
4D: oH Pre-Alarm Time Limit
Setting
Function
4D
oH Pre-Alarm Time
Limit
Note:
Refer to "L8-03: Overheat Pre-Alarm Ope Selection" for more information.
4E: Braking Transistor Fault (rr)
Setting
Function
4E
Braking Transistor
Fault (rr)
4F: Braking Resistor Overheat (oH)
Setting
Function
4F
Braking Resistor
Overheat (oH)
The braking resistor overheats when the deceleration time is short and the motor regeneration energy is
significant.
60: Internal Cooling Fan Alarm
Setting
Function
60
Internal Cooling Fan
Alarm
61: RotorPosition Detection Complete
Setting
Function
61
RotorPosition
Detection Complete
62: MEMOBUS Register 1 (H2-07&H2-08)
Setting
Function
62
MEMOBUS Register
1 (H2-07&H2-08)
63: MEMOBUS Register 2 (H2-09&H2-10)
Setting
Function
63
MEMOBUS Register
2 (H2-09&H2-10)
65: Standby output
Setting
Function
65
Standby output
798
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when L8-03 = 4 [Overheat Pre-Alarm Ope Selection = Run@L8-19 Rate]
and oH [Heatsink Overheat] does not clear even after the drive diminishes the frequency for 10
cycles.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the braking transistor integrated into the drive overheats and rr
[Dynamic Braking Transistor] is detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the braking resistor overheats and rH [Braking Resistor Overheat] is
detected.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when a failure is detected in the cooling fan inside the drive.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the Run command is input into the drive and the drive detects the
motor magnetic pole position of the PM motor.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the bit specified by H2-07 turns on regarding the MEMOBUS register
address configured with H2-08.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the bit specified by H2-10 turns on regarding the MEMOBUS register
address configured with H2-09.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off after the drive stops operating and the time set with b8-51 [Standby Mode
Wait Time] elapses.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV

Advertisement

Table of Contents
loading

Table of Contents