10.9

F: Options

F1: PG Speed Control Card (Encoder)

No.
Name
(Hex.)
F1-01
PG 1 Pulses Per
Revolution
(0380)
F1-02
PG Feedback Loss
Selection
(0381)
F1-03
Operation Select at
Overspeed
(0382)
F1-04
Operation
Selection at
(0383)
Deviation
F1-05
PG 1 Rotation
Selection
(0384)
F1-06
PG1 Division Rate
for Pulse Mon
(0385)
F1-08
Overspeed
Detection Level
(0387)
F1-09
Overspeed
Detection Delay
(0388)
Time
F1-10
Speed Deviation
Detection Level
(0389)
F1-11
Speed Deviation
Detect DelayTime
(038A)
F1-12
PG 1 Gear Teeth 1
(038B)
F1-13
PG 1 Gear Teeth 2
(038C)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of output pulses per revolution of the encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor operation when PGo [PG Disconnect] is detected.
0 : Ramp to stop
1 : Coast to stop
2 : Fast Stop (use C1-09)
3 : Alarm only
4 : No alarm display
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor operation when oS [Overspeed] is detected.
0 : Ramp to stop
1 : Coast to stop
2 : Fast Stop (use C1-09)
3 : Alarm only
4 : No alarm display
V/f
CL-V/f
OLV
CLV
AOLV
Selects the motor operation when dEv [Speed Deviation] is
detected.
0 : Ramp to stop
1 : Coast to stop
2 : Fast Stop (use C1-09)
3 : Alarm only
V/f
CL-V/f
OLV
CLV
AOLV
Selects the output sequence for phases A and B of the pulses output
from the encoder, given that the motor is running forward.
0 : Pulse A leads
1 : Pulse B leads
V/f
CL-V/f
OLV
CLV
AOLV
Sets the dividing ratio for monitor signals output from the encoder
option card.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level of oS [Overspeed] as a percentage when the
maximum output frequency is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for oS [Overspeed].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level of dEv [Speed Deviation] as a percentage
when the maximum output frequency is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection time for dEv [Speed Deviation].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth (gear ratio) between the motor and
encoder, in combination with F1-13 [PG 1 Gear Teeth 2]. F1-12 is
set with the number of gear teeth for the motor side.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of gear teeth (gear ratio) between the motor and
encoder, in combination with F1-12 [PG 1 Gear Teeth 1]. Parameter
F1-13 is set with the number of gear teeth for the load side.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM

10.9 F: Options

Default
Ref.
(Range)
600 ppr
712
(1 - 60000 ppr)
1
712
(0 - 4)
1
712
(0 - 3)
3
713
(0 - 3)
Determined by A1-
713
02
(0, 1)
001
713
(001 - 032, 102 -
132 (1 - 1/32))
115%
714
(0 - 120%)
Determined by A1-
714
02
(0.0 - 2.0 s)
10%
714
(0 - 50%)
0.5 s
714
(0.0 - 10.0 s)
0
714
(0 - 1000)
0
715
(0 - 1000)
429
10