YASKAWA GA700 Technical Manual page 428

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.8 E: Motor Parameters
No.
Name
(Hex.)
E9-04
Base Frequency
(11E7)
E9-05
Base Voltage
(11E8)
E9-06
Motor Rated
Current
(11E9)
E9-07
Motor Rated Power
(kW)
(11EA)
E9-08
Motor Pole Count
(11EB)
E9-09
Motor Rated Slip
(11EC)
E9-10
Motor Line-to-Line
Resistance
(11ED)
428
Description
V/f
CL-V/f
OLV
CLV
AOLV
Configures the rated frequency of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the rated voltage of the motor.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated current in amperes.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated power in 0.01 kW. (1 HP = 0.746 kW)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the motor rated slip.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the line-to-line resistance for motor stator windings.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
Determined by E9-
708
01
(40.0 - 120.0 Hz)
Determined by E9-
709
01
(200 V Class: 0.0
to 255.0 V,
400 V Class: 0.0 to
510.0 V)
Determined by E9-
219
01 and o2-04
(10% to 200% of
the drive rated
current)
Determined by E9-
709
02 and o2-04
(0.00 - 650.00 kW)
4
709
(2 to 48)
0.0 Hz
709
(0.0 - 20.0 Hz)
Determined by o2-
710
04
(0.000 - 65.000 Ω)