YASKAWA GA700 Technical Manual page 374

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

9.5 Drive Specifications
Item
1000 m (3281 ft) maximum
Note:
Derate the output current by 1% for every 100 m (328 ft.) to install the drive in altitudes between 1000 to 3000 m
(3281 to 9843 ft.).
Altitude
Rated voltage derating is not required:
• when installing the drive at 2000 m (6562 ft.) or lower
• if the drive is grounded with the neutral network when installing the drive at an altitude between 2000 to 3000 m
(6562 to 9843 ft.)
Contact Yaskawa or your nearest sales representative when the drive is not grounded with the neutral network.
• 10 Hz to 20 Hz: 1 G (9.8 m/s
• 20 Hz to 55 Hz:
Shock
2004 to 2211, 4002 to 4168: 0.6 G (5.9 m/s
2257 to 2415, 4208 to 4675: 0.2 G (2.0 m/s
Installation
Install the drive upright to allow for proper cooling.
Orientation
Item
• UL 61800-5-1
• EN 61800-3
Harmonized
• IEC/EN 61800-5-1:2007
Standard
• Two Safe Disable inputs and one EDM output according to ISO/EN13849-1 Cat.III PLe, IEC/EN61508 SIL3 (multi-
function digital output)
Open-chassis type (IP20)
Enclosed wall-mounted type (UL Type 1)
Protection
Note:
Design
Installing UL Type 1 kit on an open-chassis type (IP20) drive to convert the drive to a wall-mount enclosure (UL
Type 1).
*1
Approval pending for models 2070 to 2415, 4044 to 4675.
*2
Approval pending for models 2138 to 2415, 4089 to 4675.
374
2
, 32.15 ft/s
2
)
Table 9.9 Standard
*1
*2
*2
*2
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Specification
2
, 19.36 ft/s
2
)
2
, 6.56 ft/s
2
)
Specification