U5: PID Monitors

No.
Name
(Hex.)
U5-01
PID Feedback
(0057)
U5-02
PID Input
(0063)
U5-03
PID Output
(0064)
U5-04
PID Setpoint
(0065)
506
Description
V/f
CL-V/f
OLV
CLV
AOLV
Displays the operation signal (register No. 0001H) from
communication option to the drive as a four-digit hexadecimal
number.
The operation signal is displayed in the following way.
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Multi-function input 8
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
V/f
CL-V/f
OLV
CLV
AOLV
Displays the lower 4 digits of the drive run count.
Note:
The drive run count appears as an 8-digit number. The upper 4
digits of U4-25 [No of Travels(H)] and the lower 4 digits of U4-
24 appears.
V/f
CL-V/f
OLV
CLV
AOLV
Displays the upper 4 digits of the drive run count.
Note:
The drive run count appears as an 8-digit number. The upper 4
digits of U4-25 and the lower 4 digits of U4-24 [No of Travels
(L)] appears.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Displays the PID control feedback value. Display units are set by
b5-20 [PID Setpoint Scaling].
Unit: 0.01%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the deviation between the PID setpoint and PID feedback
(the amount of PID input) as a percentage of the maximum output
frequency.
Unit: 0.01%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the PID control output as a percentage of the maximum
output frequency.
Unit: 0.01%
V/f
CL-V/f
OLV
CLV
AOLV
Displays the PID setpoint. Display units are set by b5-20 [PID
Setpoint Scaling].
Unit: 0.01%
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
MFAO Signal
Ref.
Level
No signal output
-
available
No signal output
-
available
No signal output
-
available
MFAO Signal
Ref.
Level
10 V: Maximum
-
frequency (-10 V
to +10 V)
10 V: Maximum
-
frequency (-10 V
to +10 V)
10 V: Maximum
-
frequency (-10 V
to +10 V)
10 V: Maximum
-
frequency (-10 V
to +10 V)

Advertisement

Table of Contents
loading

Table of Contents