Third and Subsequent Rows: Log Data
The following example illustrates the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,0000,0000,00000C
No.
Item
1
Attribute
2
File number
3
Time stamp
4
Log Monitor Data 1
5
Log Monitor Data 2
:
:
13
Log Monitor Data 10
14
Reserved
15
Encoding data
16
Row number
o5-01: Log Start/Stop Selection
No.
Name
(Hex.)
o5-01
Log Start/Stop
Selection
(1551)
RUN
0 : OFF
Stops the data log.
1 : ON
Starts the data log in accordance with the sampling cycle configured with o5-02.
o5-02: Log Sampling Interval
No.
Name
(Hex.)
o5-02
Log Sampling
Interval
(1552)
RUN
o5-03: Log Monitor Data 1
No.
Name
(Hex.)
o5-03
Log Monitor Data 1
(1553)
RUN
Note:
Select 101 to 855 [U1-01 to U8-55] to specify log data. For example, to display U1-05 [Motor Speed], set o5-08 = 105. Set the
parameter to 000 when you do not wish to select any data log monitors. U2 monitor [Fault Trace] and U3 Monitor [Fault History]
cannot be selected.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Number of
characters
2
[02] represents that the record is a monitor data record.
4
The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number generated in
hexadecimal format.
12
Data log data was retrieved (YYMMDDHHMMSS)
4
Log monitor data (Hex.) of the monitor selected with o5-03 [Log Monitor Data 1]
4
Log monitor data (Hex.) of the monitor selected with o5-04 [Log Monitor Data 2]
:
:
4
Log monitor data (Hex.) of the monitor selected with o5-12 [Log Monitor Data 10]
4
-
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 represent the encoding of log monitor data 1 1 through 10. A bit value of 1
represents that the data represents a negative value. (Log monitor data 1 through 10 is
absolute value data without encoding)
Example when log monitor data 2, 5, and 8 represent negative values: Bits 1, 4, and 7 have
values of 1, and so the encoding data = 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
V/f
CL-V/f
OLV
CLV
Starts or stops the data log function. This parameter is only enabled for LED
keypads.
V/f
CL-V/f
OLV
CLV
Selects the data log sampling cycle. This parameter is only enabled for LED
keypads.
V/f
CL-V/f
OLV
CLV
Configures the data log monitor. This parameter is only enabled for LED
keypads.
11.11 o: Keypad-Related Settings
Description
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
0
(0, 1)
Default Setting
(Setting Range)
1000 ms
(100 - 60000 ms)
Default Setting
(Setting Range)
101
(000,101 - 855)
11
913