10.10 H: Terminal Functions
Setting
Function
D
PG Encoder
Disable
E
ASR Integral Reset
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
16
Motor 2 Selection
17
Fast Stop (N.C.)
18
Timer Function
Input
19
PID Disable
1A
Accel/Decel Time
Selection 2
446
V/f
CL-V/f
OLV
CLV
AOLV
Disregards feedback control from the encoder and runs V/f Control run if the terminal is
turned ON. Controls the motor speed using feedback from the encoder if the terminal is
turned OFF.
ON : Speed feedback control disable (V/f Control)
OFF : Speed feedback control enable (Closed Loop V/f Control)
V/f
CL-V/f
OLV
CLV
AOLV
Resets the integral value and switches the speed control loop between PI control and P
control.
ON : P control
OFF : PI control
V/f
CL-V/f
OLV
CLV
AOLV
Set when a terminal is not used or when using a terminal in through mode.
V/f
CL-V/f
OLV
CLV
AOLV
It is paired with setting value 11 (Down command). When using the Up command and
Down command, the user can raise and lower the frequency reference of the drive using
two push buttons.
ON : Raises the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
It is paired with setting value 10 (Up command). When using the Up command and
Down command, the user can raise and lower the frequency reference of the drive using
two push buttons.
ON : Lowers the frequency reference.
OFF : Holds the current frequency reference.
V/f
CL-V/f
OLV
CLV
AOLV
Inputting the Forward JOG command runs the motor in the forward direction at the jog
frequency set in d1-17 [Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
Inputting the Reverse JOG command reverses the motor at the jog frequency set in d1-17
[Jog Reference].
V/f
CL-V/f
OLV
CLV
AOLV
When the terminal is ON while the Run command is inactive, the fault currently detected
by the drive will be reset.
Note:
The fault reset signal is disregarded when the Run command is enabled. Remove the
Run command before attempting to clear a fault situation.
V/f
CL-V/f
OLV
CLV
AOLV
When Fast Stop (N.O.) is input while the drive is running, the drive performs ramp to
stop in a deceleration time configured with C1-09 [Fast Stop Time].
V/f
CL-V/f
OLV
CLV
AOLV
Switches between motors 1 and 2. Switch between motors when they are stopped.
ON : Selects motor 2
OFF : Selects motor 1
V/f
CL-V/f
OLV
CLV
AOLV
When Fast Stop (N.C.) is input while the drive is running, the drive performs ramp to
stop in a deceleration time configured with C1-09 [Fast Stop Time].
V/f
CL-V/f
OLV
CLV
AOLV
Used as the input terminal for the timer function. It is paired with Timer Output [H2-xx =
12].
V/f
CL-V/f
OLV
CLV
AOLV
Disables PID control using an external input when b5-01 = 1 to 8 [PID Function Setting
= Enabled].
ON : PID control disabled
OFF : PID control enabled
V/f
CL-V/f
OLV
CLV
AOLV
It is used in combination with the Accel/decel Time Selection 1 [H1-xx = 7]. Switches
between C1-01 to C1-08 [Acceleration and Deceleration Times 1 to 4].
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Ref.
760
760
760
760
762
762
762
763
763
763
764
764
765
765