YASKAWA GA700 Technical Manual page 679

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Note:
To use the combination of the frequency reference hold function and the Up/Down 2 function, configure the Up/Down 2 upper limit
[d4-08] and lower limit [d4-09] correctly.
Clearing the Saved Freq Reference Value
The way to clear the saved frequency reference value varies depending on which function is combined. Clear the
values with any of the following methods.
• Releasing the input programmed for Accel/Decel Ramp Hold [H1-xx = A].
• Setting an Up or Down command while no Run command is active.
• Use the Up/Down 2 Command to set d4-06 = 0.0. Or, set d4-06 = 0.0 during stop.
d4-03: Up/Down 2 Bias Level
No.
Name
(Hex.)
d4-03
Up/Down 2 Bias
Level
(02AA)
RUN
The operation depends on the set value:
• Setting d4-03 = 0.00 Hz
While Up/Down 2 Command [H1-xx = 75, 76] is ON, the bias value is increased or decreased using the accel/
decel times determined by d4-04 [Up/Down 2 Ramp Selection].
• Setting d4-03 ≠ 0.00 Hz
Every time Up/Down 2 Command [H1-xx = 75, 76] is switched ON, the bias is increased or decreased in steps
for the value set in d4-03. When the bias is increased or decreased, the acceleration and deceleration times set in
d4-04 are applied.
d4-04: Up/Down 2 Ramp Selection
No.
Name
(Hex.)
d4-04
Up/Down 2 Ramp
Selection
(02AB)
RUN
0 : Use selected Accel/Decel time
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Sets the bias added to or subtracted from the frequency reference by the Up/
Down 2 function.
Figure 11.63 Up/Down 2 Bias when d4-03 = 0.00 Hz
Figure 11.64 Up/Down 2 Bias when d4-03 ≠ 0.00 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Selects the acceleration and deceleration times to use when adding or
subtracting the bias to/from the frequency reference when using the Up/
Down 2 function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.5 d: Reference Settings
Default
(Range)
0.00 Hz
(0.00 - 99.99 Hz)
Default
(Range)
0
(0, 1)
11
679