YASKAWA GA700 Technical Manual page 899

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

Parameters o1-10 and o1-11 can be used to configure the unit of measure as desired when o1-03 = 3. Parameter
o1-10 is set to the value resulting from removing the decimal point from the maximum output frequency.
Parameter o1-11 is set to the number of digits after the decimal point in the maximum output frequency.
To display a maximum output frequency of 100.00, set the following parameters as follows.
• o1-10 = 10000
• o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
o1-04: V/f Pattern Display Unit
No.
Name
(Hex.)
o1-04
V/f Pattern Display
Unit
(0503)
Note:
• Select the setting unit of the following parameters for motor 1.
–E1-04 [Maximum Output Frequency]
–E1-06 [Base Frequency]
–E1-07 [Mid Point A Frequency]
–E1-09 [Minimum Output Frequency]
–E1-11 [Mid Point B Frequency]
–E9-02 [Motor Max Revolutions]
–E9-04 [Motor Rated Frequency]
• Select the setting unit of the following parameters for motor 2.
–E3-04 [Motor 2 Maximum Output Frequency]
–E3-06 [Motor 2 Base Frequency]
–E3-07 [Motor 2 Mid Point A Frequency]
–E3-09 [Motor 2 Minimum Output Frequency]
–E3-11 [Motor 2 Mid Point B Frequency]
0 : Hz
1 : r/min
The number of motor poles must be configured for the following parameters if o1-04 = 1 [r/min].
• E2-04 [Motor Pole Count]
• E4-04 [Motor 2 Motor Poles]
• E5-04 [PM Motor Pole Count]
• E9-08 [Motor Pole Count]
o1-05: LCD Contrast adjustment
No.
Name
(Hex.)
o1-05
LCD Contrast
adjustment
(0504)
RUN
Reducing the setting value decreases the contrast of the LCD display. Increasing the setting value increases the
contrast.
o1-10: User-Set Display Units Max Value
No.
Name
(Hex.)
o1-10
User-Set Display
Units Max Value
(0520)
To display a maximum output frequency of 100.00, set the following parameters as follows.
• o1-10 = 10000
• o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Select the setting unit of parameters that configure the V/f pattern
frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the LCD display contrast.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the value displayed for the maximum output frequency.
11.11 o: Keypad-Related Settings
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Setting Range)
Determined by A1-02
(0, 1)
Default Setting
(Setting Range)
3
(0 - 5)
Default Setting
(Setting Range)
Determined by o1-03
(1 - 60000)
11
899