Setting
Function
13
Speed Agree 2
14
User-set Speed
Agree 2
15
Frequency
Detection 3
16
Frequency
Detection 4
17
Torque Detection 1
(N.C.)
18
Torque Detection 2
(N.O.)
19
Torque Detection 2
(N.C.)
1A
During Reverse
1B
During Baseblock
(N.C.)
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is within the range of the frequency
reference ± L4-04 [Speed Agree Detection Width (+/-)].
Note:
The motor speed is used as the reference when using Closed Loop Vector Control or
Closed Loop Vector Control for PM.
ON : The output frequency is within the range of "frequency reference ± L4-04."
OFF : The output frequency is not within the range of "frequency reference ± L4-04."
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is within the range of L4-03 [Speed
Agree Detect Level (+/-)] ± [L4-04 [Speed Agree Detect Width (+/-)] and within the
range of the frequency reference ± L4-04.
ON : The output frequency is within the range of "L4-03 ± L4-04" and the range of the
frequency reference ± L4-04.
OFF : The output frequency is not within the range of "L4-03 ± L4-04" or the range of
frequency reference ± L4-04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off when the output frequency is higher than the value of "L4-03
[Speed Agree Detect Level (+/-)] + L4-04 [Speed Agree Detect Width (+/-)]." After the
terminal turns off, the terminal continues to remain off until the output frequency reaches
the level set with L4-03.
Note:
• The detection level configured with L4-03 is a signed value. Detections only occur
one specific orientation.
• The motor speed is used as the reference when using Closed Loop Vector Control or
Closed Loop Vector Control for PM.
ON : The output frequency is less than the value of L4-03 or does not exceed the value of
L4-03 + L4-04.
OFF : The output frequency exceeds the value of L4-03 + L4-04.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is higher than the value of L4-03 [Speed
Agree Detect Level (+/-)]. After the terminal turns on, the terminal continues to stay on
until the output frequency reaches the value of L4-03 - L4-04.
ON : The output frequency exceeds the value of L4-03.
OFF : The output frequency is less than the value of "L4-03 - L4-04," or it does not
exceed the value of L4-03.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off when an overtorque/undertorque situation is detected.
OFF : The output current/torque exceeds the torque value set with L6-02 [Torque
Detection Level 1], or the level has dropped and remained in this state longer than the
time set with L6-03 [Torque Detection Time 1].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when an overtorque/undertorque situation is detected.
ON : The output current/torque exceeds the torque value set with L6-05 [Torque
Detection Level 2], or the level has dropped and remained in this state longer than the
time set with L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off when an overtorque/undertorque situation is detected.
OFF : The output current/torque exceeds the torque value set with L6-05 [Torque
Detection Level 2], or the level has dropped and remained in this state longer than the
time set with L6-06 [Torque Detection Time 2].
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the motor runs in reverse.
ON : The motor is running in reverse.
OFF : The motor is running forward or is stopped.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns off during baseblock. When the drive is in the baseblock state, the
drive output transistor stops switching, and the DC bus voltage is not output.
ON : The drive is not in the baseblock state.
OFF : During baseblock
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
10.10 H: Terminal Functions
Ref.
790
791
791
792
792
793
793
793
793
10
455