H3: Mfai Parameters - YASKAWA GA700 Technical Manual

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
MEMOBUS Multi-Function AI1 to 3 Function Selection
Allows the MFAI function to be assigned to MEMOBUS register15C1 to 15C3 (Hex.) [MEMOBUS Multi-
Function AI1 to AI3 Command]. Select the function with H3-40 to H3-42 [Extend MFAI1 to MFAI3 function
selection] and set the input filter with H3-43 [Fiter time for MFAI].
Register No.
(Hex.)
15C1
15C2
15C3
*1
Set as 100%= 4096.
Figure 11.101 Functional Block Diagram for MEMOBUS Multi-Function AI Command 1
Note:
• Refer to H3-xx "MFAI Setting Values" for the analog input setting values.
• Set H3-40 to H3-42 = F when not using the terminal. The through mode function is not supported.
• The following MFAI terminals cannot be selected with H3-40 to H3-42.
H3-xx Setting Value

H3: MFAI Parameters

H3-01: Terminal A1 Signal Level Select
No.
Name
(Hex.)
H3-01
Terminal A1 Signal
Level Select
(0410)
0 : 0-10V (LowLim=0)
The voltage signal is 0 Vdc to 10 Vdc. The minimum input level is limited to 0%, so that a negative input signal
due to gain and bias settings will be read as 0%.
1 : 0-10V (BipolRef)
The voltage signal is 0 Vdc to 10 Vdc. Signals of both positive and negative polarities are enabled. When this
setting is used as the frequency reference, the motor runs reverse when the Forward run command is input, or runs
forward when the Reverse run signal is input, while the signal is a negative number due to gain and bias.
2 : 4-20 mA
The current signal is 4 mA to 20 mA. The minimum input level is limited to 0%, so that a negative input signal
due to gain and bias settings will be read as 0%.
802
Table 11.54 MEMOBUS Multi-Function AI Command Register
Name
MEMOBUS Multi-Function AI1
Command
MEMOBUS Multi-Function AI2
Command
MEMOBUS Multi-Function AI3
Command
0
1
2
3
30
31
32
V/f
CL-V/f
OLV
CLV
Selects the input signal level for MFAI terminal A1.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Setting Range
*1
-32767 - 32767
-32767 - 32767
-32767 - 32767
Frequency Bias
Frequency Gain
Auxiliary Frequency Reference 1
Auxiliary Frequency Reference 2
DriveWorksEZ Analog Input 1
DriveWorksEZ Analog Input 2
DriveWorksEZ Analog Input 3
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Parameters
H3-40
H3-41
H3-42
Function
Default
(Range)
0
(0 - 3)

Advertisement