11.11 o: Keypad-Related Settings
o1-01: Drive Mode Unit Monitor Select
No.
Name
(Hex.)
o1-01
Drive Mode Unit
Monitor Select
(0500)
RUN
Each time the
on the keypad is pressed while the drive is in Drive Mode, the monitor item selected by o1-01
switches in order of frequency reference, direction of motor rotation, output frequency, and output current.
Configure the x-xx portion of the monitoring parameter Ux-xx that appears in the fifth position for the Drive
Mode. For example, to display U1-05 [Motor Speed], set o1-01 = 105.
Note:
• U2 monitor [Fault Trace] and U3 Monitor [Fault History] cannot be selected.
• The selectable monitors vary depending on the control method.
o1-02: User Monitor Select afterPowerUp
No.
Name
(Hex.)
o1-02
User Monitor Select
afterPowerUp
(0501)
RUN
1 : Frequency reference (U1-01)
2 : Direction
3 : Output frequency (U1-02)
4 : Output current (U1-03)
5 : UserSelect Monitor(set by o1-01)
Displays the monitor item selected by o1-01 [Drive Mode Unit Monitor Select].
o1-03: Keypad Display Selection
No.
Name
(Hex.)
o1-03
Keypad Display
Selection
(0502)
Note:
When the setting value of o1-03 is changed, the following monitor and parameter units change as well.
• U1-01 [Freq Reference]
• U1-02 [Output Frequency]
• U1-05 [Motor Speed]
• U1-16 [SFS Output Frequency]
• d1-01 to d1-17 [Reference 1 to 17]
0 : 0.01 Hz
1 : 0.01% (100% = E1-04)
The maximum output frequency is 100%.
2 : r/min
Calculated automatically based on the maximum output frequency and number of motor poles.
Note:
If o1-03 = 2 [r/min], be sure to set the number of motor poles to the following parameters.
• E2-04 [Motor Pole Count]
• E4-04 [Motor 2 Motor Poles]
• E5-04 [PM Motor Pole Count]
• E9-08 [Number of Poles]
3 : User-selected units
898
V/f
CL-V/f
OLV
CLV
AOLV
Configure the U monitor that appears for the Drive Mode. This parameter is
only enabled for LED keypads.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the monitor item initially displayed when the drive is energized.
Refer to "U: Monitors" for more information on monitor items that can be
displayed. This parameter is only enabled for LED keypads.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the display units for the frequency reference and output frequency.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default Setting
(Setting Range)
106
(104 - 855)
Default Setting
(Setting Range)
1
(1 - 5)
Default Setting
(Setting Range)
Determined by A1-02
(0 - 3)