YASKAWA GA700 Technical Manual page 639

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

b8-18: E-Save d-axis Current FilterTime
No.
Name
(Hex.)
b8-18
E-Save d-axis
Current FilterTime
(01FA)
b8-19: E-Save Search Injection Freq
No.
Name
(Hex.)
b8-19
E-Save Search
Injection Freq
(0B40)
Note:
• If the machine vibrates due to low inertia, increase the setting value in increments of 10 Hz while checking the responsiveness. If A1-
02 = 8 [Control Method Selection = EZ Open Loop Vector Control], increase the setting value in increments of 1 Hz.
• To improve motor efficiency, reduce the setting value in increments of 1 Hz until the point just before machine vibration begins to
occur.
b8-20: PM E-Save Search Width
No.
Name
(Hex.)
b8-20
PM E-Save Search
Width
(0B41)
Increasing the value may improve operational efficiency. However, adjustment may be necessary to prevent
machine vibration if the load inertia is small.
Note:
• If the machine vibrates due to low inertia, reduce the setting value in increments of 1.0 degrees while checking the responsiveness.
• To improve motor efficiency, increase the setting value in increments of 1.0 degrees until the point just before machine vibration begins
to occur.
b8-21: PM E-Save Search Gain
No.
Name
(Hex.)
b8-21
PM E-Save Search
Gain
(0B42)
When the value of C5-01 [ASR Proportional Gain 1] is reduced, make sure to also reduce the value of b8-21 to
maintain the correct ratio.
b8-22: PM E-Save Search LPF Cutoff Freq
No.
Name
(Hex.)
b8-22
PM E-Save Search
LPF Cutoff Freq
(0B43)
b8-23: PM E-Save Search Limit
No.
Name
(Hex.)
b8-23
PM E-Save Search
Limit
(0B44)
Depending on the motor characteristics, increasing this value may improve efficiency.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
Configures the d-axis current reference filter time constant.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the energy-saving control search operation frequency. Normally
there is no need to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the amplitude of energy-saving control search operations.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the gain of search operations.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the frequency of the filter used to extract the high-efficiency
phase from search operations. Normally there is no need to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Configures the limit value of search operation output. Normally there is no
need to change this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.3 b: Application
Default Setting
(Range)
0.100 s
(0.000 - 5.000 s)
Default Setting
(Range)
Determined by A1-02
(20 - 300 Hz)
Default Setting
(Range)
1.0 degrees
(0.1 to 5.0 degrees)
Default Setting
(Range)
0.3Hz
(0.1 - 20.0 Hz)
Default Setting
(Range)
10.0 Hz
(1.0 - 30.0 Hz)
Default Setting
(Range)
15.0 degrees
(0.0 to 30.0 degrees)