6.4 Fault
Code
Name
Err
EEPROM Write Error
Note:
Perform Fault Reset to clear the fault.
Code
Name
FAn
Internal Fan Fault
Note:
Perform Fault Reset to clear the fault.
Code
Name
FAn1
Drive cooling fan failure
Note:
Perform Fault Reset to clear the fault.
Code
Name
FbH
Excessive PID Feedback
Note:
• Detected if PID feedback input has exceeded the level set in b5-36 [PID Feedback High Detection Lvl] for longer than b5-37 [PID
Feedback High Detection Time].
• Perform Fault Reset to clear the fault.
• If detected, the drive will operate the motor according to the stop method set in b5-12 [Feedback Loss Detection Select].
Code
Name
FbL
PID Feedback Loss
280
Cause
An EEPROM hardware problem
occurred.
Noise has corrupted data while writing
to the EEPROM of the drive.
Cause
The circulation fan has malfunctioned.
A fault detected in the power supply of
the electromagnetic contactor and the
circulation fan.
Cause
The cooling fan has malfunctioned.
Cause
The FbH detection level has not been
set appropriately.
The PID feedback wiring is faulty.
Feedback sensor has malfunctioned.
A fault occurred in the feedback input
circuit of the drive.
Cause
The FbL detection level has not been set
appropriately.
The PID feedback wiring is faulty.
Feedback sensor has malfunctioned.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Possible Solution
• Re-energize the drive and check if the fault still
remains.
• Replace either the control board or the entire
drive if the fault continues. For instructions on
replacing the control board, contact Yaskawa or
your nearest sales representative.
• Press
.
• Set the parameters again.
Possible Solution
• Check for circulation fan operation.
• Restart the drive and check if the fault still
remains.
• Check U4-03 [Cooling Fan Ope Time] and U4-
04 [Cool Fan Maintenance]. If the circulation
fan has exceeded its expected performance life
or is damaged in any other way, follow the
replacement instructions in this manual.
• Re-energize the drive and check if the fault still
remains.
• Replace either the control board or the entire
drive if the fault continues. For instructions on
replacing the control board, contact Yaskawa or
your nearest sales representative.
Possible Solution
• Check to see if the cooling fan is operating.
• Restart the drive and check if the fault still
remains.
• Check U4-03 [Cooling Fan Ope Time] and U4-
04 [Cool Fan Maintenance]. If the cooling fan
has exceeded its expected performance life or is
damaged in any way, replace it according to the
instructions in this manual.
Possible Solution
Adjust b5-36 and b5-37.
Correct any PID control wiring errors.
Check the state of the sensors on the control device
side.
Replace the board or the entire drive. For
instructions on replacing the control board, contact
Yaskawa or your nearest sales representative.
Possible Solution
Adjust b5-13 and b5-14.
Correct any PID control wiring errors.
Check the state of the sensors on the control device
side.