H4: Analog Outputs

H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias,
and select output signal levels.
Calibration of Meters Connected to Multi-function Analog Output Terminals FM and
AM
Meters connected to terminals FM and AM can be calibrated using H4-02, H4-03, H4-05, and H4-06 [FM/AM
Analog Output Gain/Bias].
No.
H4-02
FM Analog Output Gain
H4-03
FM Analog Output Bias
H4-05
AM Analog Output Gain
H4-06
AM Analog Output Bias
H4-07
MFAO Term FM Signal Level Select
H4-08
MFAO Term AM Signal Level Select
The following diagram illustrates the gain and bias.
For example, when the parameter value configured to analog output is 0 and a 3 V signal is output to terminal FM,
H4-03 [FM Analog Output Bias] is set to 30%.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
Used with DriveWorksEZ. Refer to the DriveWorksEZ Online Manual for more information.
Name
Figure 11.108 Analog Output Gain/Bias Configuration Example 1
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Setting Range
-999.9 - 999.9%
-999.9 - 999.9%
-999.9 - 999.9%
-999.9 - 999.9%
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
11.8 H: Terminal Functions
Default Setting
100.0%
0.0%
50.0%
0.0%
0
0