YASKAWA GA700 Technical Manual page 774

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

11.8 H: Terminal Functions
Frequency
Func
reference
tion
source
8
9
Others
(Analog input,
transmission)
10
76: Down 2 Command
Setting
Function
76
Down 2 Command
If the input terminal set for the Up 2 Command is turned ON, the bias increases, and if the terminal set for the
Down 2 Command is turned ON, the bias decreases. When both commands are turned ON or OFF, the frequency
reference is held.
Note:
• When the Up2/Down2 function is used, set the optimal bias limit value using d4-08 and d4-09 [Up/Down 2 Bias Upper Limit/Lower
Limit (Up/Down 2)].
• Refer to "d4: FreqRef Hold&Up/Down Func" for details.
77: ASR Gain Switch
Setting
Function
77
ASR Gain Switch
ON : C5-03
Switches the proportional gain to C5-03 [ASR Proportional Gain 2].
OFF : C5-01
Switches the proportional gain to C5-01 [ASR Proportional Gain 1].
Note:
Refer to "C5: Automatic Speed Regulator (ASR)" for details.
78: Ex.Torque Ref Polarity Inversion
Setting
Function
78
Ex.Torque Ref
Polarity Inversion
ON : External torque reference reverse direction
OFF : External torque reference forward direction
774
d4-03
d4-05
d4-01
• The drive accelerates the motor
• The drive decelerates the motor
0
1
-
• In any other state, the drive operates
0
• The drive accelerates the motor up to
• The drive decelerates the motor up to
> 0
-
1
• During acceleration or deceleration,
V/f
CL-V/f
OLV
Decelerates the motor by reducing the frequency reference bias value when the terminal is turned
ON. Always set the Up2 command and Down 2 command as a pair.
V/f
CL-V/f
OLV
Switches the ASR proportional gain set in C5-01 [ASR Proportional Gain 1] and C5-03 [ASR
Proportional Gain 1/2].
V/f
CL-V/f
OLV
Switches the rotation direction of the external torque reference.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Operation
while the Up 2 command is turned
ON. (increases the bias value)
while the Down 2 command is
turned ON. (reduces the bias value)
following the frequency reference.
"Freq Reference + d4-03" while the
Up 2 command is turned ON. (the
bias value increases up to the value
set in d4-03)
"Freq Reference + d4-03" while the
Down 2 command is turned ON. (the
bias value reduces to the value set in
d4-03)
when the frequency reference is
changed to a value other than that set
in d4-07, the drive holds the bias
value until the output frequency and
the actual frequency reference match
(speed agreement).
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Storing the frequency reference
or frequency bias
Not stored.
Not stored.
When the bias value is constant within
5 seconds after frequency reference
hold starts, the bias value being held is
stored in d4-06. Rewriting the
frequency reference is not possible.
Only the bias value is stored.