A - External power, 48 V max.
B - Flywheel diode
Termi
Type
nal
Pulse Train Output
MP
(Output frequency)
Analog monitor output 1
FM
(Output frequency)
Monitor
output
Analog monitor output 2
AM
(Output current)
AC
Monitor common
External power supply input terminals
The following table lists the functions of the external power supply input terminals.
Type
External power supply
input terminals
Serial Communication Terminals
Refer to
Table 2.22
for a list of serial communication terminals and functions.
Type
Terminal
MEMOBUS/Modbus
communications

Control Circuit Terminal Configuration

Control circuit terminals should are arranged as shown in the following figure.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
Figure 2.44 Connecting a Flywheel Diode
Table 2.20 Control Circuit Monitor Output Terminals
Name (Default)
Table 2.21 External power supply input terminals
Terminal
Name (Default)
External 24 V power supply
PS
input
External 24 V power supply
AC
ground
Table 2.22 Serial Communication Terminals
Terminal
Name
Communica
MEMOBUS/Modbus communications
D+
tion input/
Use an RS-485 cable to connect the
output (+)
drive.
Note:
Set DIP switch S2 to ON to enable
Communica
D-
the termination resistor in the last
tion output (-)
drive in a MEMOBUS/Modbus
network.
AC
Shield ground 0 V
C - Coil
D - 50 mA or less
Function (Signal Level)
32 kHz max.
Refer to "Pulse Train Output" for details.
Voltage or current output
• 0 V to 10 V/0% to 100%
• -10 V to 10 V/-100% to 100%
• 4 mA to 20 mA
Note:
Select using jumper switch S5 and H4-07 [MFAO Term FM Signal
Level Select] or H4-08 [MFAO Term AM Signal Level Select].
0 V
Supplies backup power to the drive control circuit, keypad,
and option board.
21.6 VDC to 26.4 VDC, 700 mA
0 V
Function (Signal Level)
2.14 Control Circuit Wiring
Function
• RS-485
• MEMOBUS/Modbus
communication protocol
• Max. 115.2 kbps
2