YASKAWA GA700 Technical Manual page 438

High performance type; 200 v class: 0.4 to 110 kw; 400 v class: 0.4 to 355 kw
Hide thumbs Also See for GA700:
Table of Contents

Advertisement

10.9 F: Options
No.
Name
(Hex.)
F6-46
BACnet Baud Rate
(02FC)
F6-47
Rx to Tx Wait
Time
(02FD)
F6-48
BACnet Device
Object Identifier0
(02FE)
F6-49
BACnet Device
Object Identifier1
(02FF)
F6-50
DN MAC Address
(03C1)
F6-51
DN Baud Rate
(03C2)
F6-52
DeviceNet PCA
Setting
(03C3)
F6-53
DeviceNet PPA
Setting
(03C4)
F6-54
DN Idle Flt Det
(03C5)
F6-55
DN BAUD RATE
MEM
(03C6)
F6-56
DeviceNet Speed
Scaling
(03D7)
F6-57
DeviceNet Current
Scaling
(03D8)
438
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the BACnet communications speed.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19.2 kbps
5 : 38.4 kbps
6 : 57.6 kbps
7 : 76.8 kbps
8 : 115.2 kbps
V/f
CL-V/f
OLV
CLV
AOLV
Sets the wait time for reception and transmission of BACnet
communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of addresses for BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the last word of addresses for BACnet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MAC address for DeviceNet communication. The drive
must be restarted when the setting is changed.
Note:
Select a MAC address that does not overlap with other nodes. Do
not set this parameter to a value of 0. If the parameter is set
incorrectly, the ERR on the option card flashes, and the drive will
detect the AEr [Node Address Setting Error] error.
V/f
CL-V/f
OLV
CLV
AOLV
Selects the communications speed for DeviceNet communication.
The drive must be restarted when the setting is changed.
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
3 : Adjustable from network
4 : Detect automatically
V/f
CL-V/f
OLV
CLV
AOLV
Sets the format of data sent from the DeviceNet communication
master to the drive.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the format of data sent from the drive to the DeviceNet
communication master.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether or not to detect issues of EF0 [Option Card
External Fault] when data is not received from the DeviceNet
master.
0 : Enabled
1 : Disabled, no fault detection
V/f
CL-V/f
OLV
CLV
AOLV
This parameter is used to enable confirmation of the currently valid
communications speed for DeviceNet communication via the
keypad. This parameter is used for monitoring only.
0 : 125 kbps
1 : 250 kbps
2 : 500 kbps
V/f
CL-V/f
OLV
CLV
AOLV
Sets the speed scale for DeviceNet communication.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the current scale of the DeviceNet communication master.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
Ref.
(Range)
3
741
(0 - 8)
5 ms
741
(5 - 65 ms)
0
741
(0 - FFFF)
0
741
(0 - 3F)
0
742
(0 - 64)
0
742
(0 - 4)
21
742
(0 - 255)
71
742
(0 - 255)
0
742
(0 - 4)
0
743
(0 - 2)
0
743
(-15 - +15)
0
743
(-15 - +15)

Advertisement

Table of Contents
loading