n8-55: Load Inertia
No.
Name
(Hex.)
n8-55
Load Inertia
(056E)
Adjust this parameter in the following circumstances.
• Gradually increase the setting value of 0 if responsiveness of torque and speed is poor.
• Gradually increase the setting value of 0 if motors do not start smoothly.
• Gradually increase the setting value of 0 if the motor stalls during run constant speed.
• Reduce the setting value if vibration or hunting issues occur.
Note:
• If the value is set too low, STPo [Pull-Out Detection] may be detected.
• Motors may vibrate if the setting value is too high when using a single motor or operating motors at low inertia.
0 : Below 1:10
Use this setting in the following scenarios.
• The ratio between the motor inertia and machine inertia is less than 1:10
• Current ripples are significant
1 : Between 1:10 and 1:30
Use this setting in the following scenarios.
• The ratio between the motor inertia and machine inertia is approximately between 1:10 to 1:30
• An STPo was detected as a result of impact load or sudden acceleration/deceleration when n8-55 = 0 was set.
2 : Between 1:30 and 1:50
Use this setting in the following scenarios.
• The ratio between the motor inertia and machine inertia is approximately between 1:30 to 1:50
• An STPo was detected as a result of impact load or sudden acceleration/deceleration when n8-55 = 1 was set.
3 : Beyond 1:50
Adjust this parameter in the following circumstances.
• The ratio between the motor inertia and machine inertia is over 1:50.
• An STPo was detected as a result of impact load or sudden acceleration/deceleration when n8-55 = 2 was set.
n8-57: High Frequency Injection
No.
Name
(Hex.)
n8-57
High Frequency
Injection
(0574)
Note:
• Excitation sound will be generated from the motor when high frequency injection is carried out.
• Set E1-09 [Minimum Output Frequency] = 0.0 when using Zero Speed Control.
0 : Disabled
Set this parameter to 0 when using SPM motors. The speed control range is approximately 1:20.
When n8-57 = 0 is set, E1-09 [Minimum Output Frequency] cannot be set to a value that is less than or equal to 1/
20 of the value of E1-06 [Base Frequency].
1 : Enabled
Set this parameter to 1 when using IPM motors. The speed control range changes to 1:100, which enables highly
accurate speed detection.
YASKAWA ELECTRIC SIEP C710617 01B YASKAWA AC Drive GA700 Technical Manual
V/f
CL-V/f
OLV
CLV
AOLV
This parameter sets the ratio between motor inertia and machine inertia.
V/f
CL-V/f
OLV
CLV
AOLV
Selects whether to perform a high frequency injection to detect motor speed.