Sub-Chart A-2 (PM Motor Auto-Tuning and Test Run Procedure)

Sub-Chart A-2 explains the basic steps to follow to start up the drive for a PM motor.
Note:
1. Although parameters for setting speed control with an encoder are also included as part of the settings made during Auto-Tuning,
F1-05 [PG 1 Rotation Selection] must be set before Auto-Tuning is started.
2. Whenever the encoder has been replaced due to failure or other reasons, make sure to perform Z Pulse Offset Tuning.
WARNING! Crash Hazard. Conduct test operations to make sure that the drive operates safely after writing work is completed
and parameters have been set. Failure to comply may cause injury or damage to equipment.