Faults and alarms
List of faults and alarms
For fault value = 208:
Check parameter p0430.23 and reset if necessary.
A01304 (F)
Firmware version of DRIVE-CLiQ component is not up-to-date
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The non-volatile memory has a more recent firmware version than the one in the connected DRIVE-CLiQ compo-
nent.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component involved.
Remedy:
Update the firmware (p7828, p7829 and commissioning software).
Reaction upon F:
NONE
Acknowl. upon F:
IMMEDIATELY
F01305
Topology: Component number missing
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The component number from the topology was not parameterized (p0121 (for power unit, refer to p0107), p0131 (for
servo/vector drives, refer to p0107), p0141, p0151, p0161).
Fault value (r0949, decimal interpretation):
Data set number.
Note:
The fault also occurs if speed encoders have been configured (p0187 to p0189) but no component numbers exist for
them.
In this case, the fault value includes the drive data set number plus 100 * encoder number (e.g. 3xx, if a component
number was not entered in p0141 for the third encoder (p0189)).
See also: p0121, p0131, p0141, p0142, p0186, p0187, p0188
Remedy:
Enter the missing component number or remove the component and restart commissioning.
See also: p0121, p0131, p0141, p0142, p0186, p0187, p0188
A01306
Firmware of the DRIVE-CLiQ component being updated
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
Firmware update is active for at least one DRIVE-CLiQ component.
Alarm value (r2124, interpret decimal):
Component number of the DRIVE-CLiQ component.
Remedy:
Not necessary.
This alarm automatically disappears after the firmware has been updated.
A01314
Topology: Component must not be present
Message value:
Component number: %1, Component class: %2, Connection number: %3
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
For a component, "de-activate and not present" is set but this component is still in the topology.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number
bb = component class of the component
cc = connection number
Note:
Component class and connection number are described in F01375.
3-992
© Siemens AG 2012 All Rights Reserved
SINAMICS S110 List Manual (LH7), 06/2012, 6SL3097-4AP10-0BP3