6 Calibration

6.5 Verifying the calibration

6.5 Verifying the calibration
Introduction
Always verify the results after calibrating any robot axis to verify that all calibration
positions are correct.
Verifying the calibration
Use this procedure to verify the calibration result.
1
2
3
586
Action
Run the calibration home position program twice.
Do not change the position of the robot axes after running
the program!
Adjust the synchronization marks when the calibration is
done, if necessary.
Write down the values on a new label and stick it on top
of the calibration label.
The label is located on one side of the base.
© Copyright 20192020 ABB. All rights reserved.
Note
See
Checking the synchron-
ization position on page
587.
This is detailed in section
Synchronization marks and
synchronization position for
axes on page
563.
Product manual - IRB 1100
3HAC064992-001 Revision: C