H4: Analog Outputs - YASKAWA FSDrive-MV1000 Parameter Manual

Super energy-saving medium-voltage ac drive, 2.4 kv class, 3 kv class, 4.16 kv class, 6 kv class, 11 kv class
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

◆ H4: Analog Outputs

These parameters assign functions to analog outputs 1 to 4 for monitoring a specific aspect of drive performance.
H4-01, H4-11, H4-21, H4-31: Analog Output 1, 2, 3, 4 Monitor Selections
Sets the desired drive monitor parameter U -
Monitors on page 70
for a list of all monitors. The "Analog Output Level" column indicates if a monitor can be used for
analog output.
Example: Enter "103" for U1-03.
No.
H4-01
Analog Output 1 Monitor Selection
H4-11
Analog Output 2 Monitor Selection
H4-21
Analog Output 3 Monitor Selection
H4-31
Analog Output 4 Monitor Selection
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as
analog output levels can be set by a PLC via a communication option card or MEMOBUS/Modbus (through mode).
H4-02, H4-03: Analog Output 1 Gain and Bias
H4-12, H4-13: Analog Output 2 Gain and Bias
H4-22, H4-23: Analog Output 3 Gain and Bias
H4-32, H4-33: Analog Output 4 Gain and Bias
Parameter H4-02, H4-12, H4-22, and H4-32 set analog outputs 1 to 4 signal level equal to 100% of the monitor (gain).
Parameter H4-03, H3-13, H3-23, H3-33 set the bias added to the monitor output for analog outputs 1 to 4. Both are set as
a percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc using parameter H4-05, H4-15, H4-25,
and H4-35.
Figure 2.68
illustrates how gain and bias settings work.
No.
H4-02
H4-03
H4-12
H4-13
H4-22
H4-23
H4-32
H4-33
YASKAWA ELECTRIC EZZ010930 FSDrive-MV1000 Parameter Guide
to output as an analog value via analog outputs 1 to 4. Refer to
Name
Name
Analog Output 1 Gain
Analog Output 1 Bias
Analog Output 2 Gain
Analog Output 2 Bias
Analog Output 3 Gain
Analog Output 3 Bias
Analog Output 4 Gain
Analog Output 4 Bias
2.7 H: Terminal Functions
Setting Range
000 to 999
000 to 999
000 to 999
000 to 999
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
U:
Default
102
103
000
000
Default
100.0%
0.0%
100.0%
0.0%
100.0%
0.0%
100.0%
0.0%
193

Advertisement

Table of Contents
loading

Table of Contents