H4: Analog Outputs; H5: Modbus Communication - YASKAWA CIPR-GA50C series Technical Manual

Ac micro drives for industrial applications. 200 v class, three-phase input: 0.1 to 22 kw. 200 v class, single-phase input: 0.1 to 4.0 kw. 400 v class, three-phase input: 0.37 to 30 kw.
Table of Contents

Advertisement

11.10 H: Terminal Functions
Setting Value
Function
14
Torque Compensation
15
General Torque Limit
16
Differential PID
Feedback
1F
Not Used
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2

H4: Analog Outputs

No.
Name
(Hex.)
H4-01
Terminal AM Analog
Output Select
(041D)
H4-02
Terminal AM Analog
Output Gain
(041E)
RUN
H4-03
Terminal AM Analog
Output Bias
(041F)
RUN
H4-07
Terminal AM Signal
Level Select
(0423)
H4-20
Analog Power Monitor
100% Level
(0B53)

H5: Modbus Communication

No.
Name
(Hex.)
H5-01
Drive Node Address
(0425)
H5-02
Communication Speed
Selection
(0426)
382
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Enters the torque compensation value if the motor rated torque is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the
motor rated torque is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use this setting for unused terminals or to use terminals in through mode.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Description
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the monitoring number to be output from the MFAO terminal AM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-
02 [Output Frequency].
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
Sets the analog signal output level from the terminal AM at 10 V or 20 mA as 100%
when an output for monitoring items is 100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the MFAO terminal AM output signal level.
Note:
Make sure that you set jumper S5 on the control circuit terminal board when you
change these parameters.
0 : 0-10V (LowLim=0)
2 : 4 to 20 mA
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the level at 10 V when U1-08 [Output Power] is set for analog output.
Description
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the communication slave address for drives.
Note:
• Restart the drive after changing the parameter setting.
• Setting 0 will not let the drive respond to MEMOBUS/Modbus communications.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the communications speed for MEMOBUS/Modbus communications.
Note:
Restart the drive after changing the parameter setting.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
Description
YASKAWA SIEPC71061753A GA500 Technical Manual
Ref.
651
651
651
652
652
652
Default
Ref.
(Range)
102
653
(000 - 999)
100.0%
653
(-999.9 - +999.9%)
0.0%
653
(-999.9 - +999.9%)
0
653
(0, 2)
0.00 kW
654
(0.00 - 650.00 kW)
Default
Ref.
(Range)
1FH
654
(0 - FFH)
3
654
(0 - 8)

Advertisement

Table of Contents
loading