Analog Outputs: H4-01 To H4-03 - YASKAWA V1000 Series Installation & Start-Up Manual

Hide thumbs Also See for V1000 Series:
Table of Contents

Advertisement

Analog Outputs: H4-01 to H4-03

Group U parameters can be used to observe the drive status (operating conditions)
through the LED operator. Analog outputs corresponding to these monitors can be
obtained on analog output terminal AM or Fm when programmed with parameter
group H4. Some Group U monitors are not available as analog outputs.
No.
Parameter Name
Multi-Function Analog 1
H4-01
(Terminal AM Monitor
Selection)
Multi-Function Analog 1
H4-02
(Terminal AM Output
<1>
Gain)
H4-03
Terminal AM Bias
Setting
<1>
Indicates that the parameter can be changed during run.
<1>
Changing Analog Output Settings
The following example illustrates how to program analog output terminal FM to
generate a signal proportional to drive output current (monitor U1-03).
Using H4-01 to Display Monitor Contents
1.
Turn on the power to the drive. The initial display appears.
Press
until the Parameter setting menu is displayed.
2.
Press
to enter the Parameter setting menu.
3.
4.
Press
and
YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
Select the data to be output through multi-function analog output
terminal AM.
Set the desired monitor parameter to the digits available in
U1-
. For example, enter "103" for U1-03.
When using this terminal as a through terminal or when not using
it at all, set "000" or "031".
Sets terminal AM output level when selected monitor is at 100%.
Maximum output voltage is 10 V (can be adjusted with a
voltmeter).
Sets the voltage level bias for terminal AM.
The bias added is 0 to ±10% with a maximum voltage output of
10 V as 100%.
Step
to select H4-01.
4.4 Basic Parameter Adjustments
Description
Page
Display/Result
153
4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents