Set Input Signals For Mfai Terminals A1 To A3 - YASKAWA GA800 600 V Drive Installation & Primary Operation

For industrial applications
Table of Contents

Advertisement

Mode
Sinking Mode (NPN)
Sourcing Mode
(PNP)

Set Input Signals for MFAI Terminals A1 to A3

Use terminals A1 to A3 to input a voltage or a current signal. Set the signal type as shown in
DIP Switch Settings
Terminal
Input Signal
Switch
Voltage input
A1
S1-1
Current input
Voltage input
A2
S1-2
Current input
Voltage input
A3
S1-3
Current input
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Internal Power Supply (Terminal SN-SP)
Figure 10.14 Location of DIP Switch S1
Table 10.9 MFAI Terminals A1 to A3 Signal Settings
Setting
No.
V
(Default)
H3-01
I
V
H3-09
I
(Default)
V
(Default)
H3-05
I
Parameter
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100% (input impedance: 20 kΩ)
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100% (input impedance: 20 kΩ)
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100% (input impedance: 20 kΩ)
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
10 Drive Start-Up Procedure
External 24 V power supply
Table
10.9.
Signal Level